6110-00-880-1963 AMPLIFIER,ELECTRONIC CONTROL Index 5950-00-880-1966 TRANSFORMER,POWER

National Stock Number:
5950-00-880-1964

Federal Supply Class:
5950

National Item Identification Number:
008801964

Description:
TRANSFORMER,POWER

Detail:
A TRANSFORMER CONSISTING OF ONE OR MORE PRIMARY WINDING(S) AND ONE OR MORE SECONDARY WINDING(S). IT MAY BE DESIGNED FOR DIRECT CONNECTION TO AN ALTERNATING CURRENT SOURCE FOR PURPOSES OF CHANGING THE SECONDARY VOLTS AND AMPERES OR DESIGNED TO ELIMINATE METALLIC INTERCONNECTION BETWEEN CIRCUITS IN AN OVERALL ONE TO ONE VOLTAGE RATIO, WITH OR WITHOUT ADDITIONAL OUTPUT WINDINGS, OR ITEMS DESIGNED TO AUTOMATICALLY MAINTAIN A CONSTANT OUTPUT VOLTAGE WITHIN SPECIFIED LIMITS UNDER VARYING INPUT OR LOAD CONDITIONS. ALSO INCLUDES ITEMS HAVING A PROVISION FOR MECHANICALLY CHANGING THE TURNS RATIO OR INDUCTIVE COUPLING IN PROGRESSIVE INCREMENTS BY MEANS OF VOLTAGE TAPS, RATIO ADJUSTER, OR DEVICES OE SIMILAR DESIGN. FOR TRANSFORMERS HAVING WINDING(S) COMMON TO BOTH INPUT AND OUTPUT CIRCUITS, SEE TRANSFORMER (1), POWER, AUTOTRANSFORMER. EXCLUDES TRANSFORMER (1), PULSE.


Manufacturer Information:
1545072964ROBERT M. HADLEY COMPANY, INC.
16P4811700A.E.YORK, LLC
7007904386MAGNETEK INC HUNTINGTON DIV
900123-18106481NORTHROP GRUMMAN SYSTEMS CORPORATION
700790LG51MAGNETEK INC LIGHTING PRODUCTS GROUP


Techincal Specification:
TERMINAL TYPE AND QUANTITY14 WIRE HOOK
WINDING OPERATING VOLTAGE12.60 AC VOLTS NOMINAL SINGLE COMPONENT 1ST SECONDARY
12.60 AC VOLTS NOMINAL SINGLE COMPONENT 2ND SECONDARY
26.00 AC VOLTS NOMINAL SINGLE COMPONENT 3RD SECONDARY
44.00 AC VOLTS NOMINAL SINGLE COMPONENT 4TH SECONDARY
115.00 AC VOLTS NOMINAL SINGLE COMPONENT SINGLE PRIMARY
WINDING OPERATING CURRENT2.0 AMPERES AC MAXIMUM SINGLE COMPONENT 1ST SECONDARY
2.0 AMPERES AC MAXIMUM SINGLE COMPONENT 2ND SECONDARY
500.0 MILLIAMPERES AC MAXIMUM SINGLE COMPONENT 3RD SECONDARY
2.0 AMPERES AC MAXIMUM SINGLE COMPONENT 4TH SECONDARY
FREQUENCY RATING400.0 HERTZ NOMINAL SINGLE COMPONENT
WINDING SHIELDING METHODINTERNAL SHIELD GROUNDED TO INCLOSURE SINGLE COMPONENT
WINDING FUNCTION AND QUANTITY1 PRIMARY AND
4 SECONDARY SINGLE COMPONENT
INPUT-OUTPUT PHASE RELATIONSHIPSINGLE PHASE TO SINGLE PHASE SINGLE COMPONENT
MOUNTING METHODTHREADED STUD SINGLE GROUP
MOUNTING FACILITY QUANTITY4 SINGLE GROUP
THREAD SERIES DESIGNATORUNC SINGLE GROUP
NOMINAL THREAD SIZE0.138 INCHES SINGLE GROUP
THREAD QUANTITY PER INCH32 SINGLE GROUP
CENTER TO CENTER DISTANCE BETWEEN MOUNTING FACILITIES PARALLEL TO LENGTH1.380 INCHES NOMINAL SINGLE MOUNTING FACILITY SINGLE CENTER GROUP
CENTER TO CENTER DISTANCE BETWEEN MOUNTING FACILITIES PARALLEL TO WIDTH1.250 INCHES NOMINAL SINGLE MOUNTING FACILITY SINGLE CENTER GROUP
INCLOSURE TYPEHERMETICALLY SEALED
BODY LENGTH1.940 INCHES NOMINAL
BODY HEIGHT2.750 INCHES NOMINAL
BODY WIDTH1.810 INCHES NOMINAL
RELIABILITY INDICATORNOT ESTABLISHED