| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 0.875 INCHES NOMINAL |
| BODY LENGTH | 1.562 INCHES NOMINAL |
| BODY STYLE | SINGLE POLE TYPE |
| BODY WIDTH | 0.656 INCHES NOMINAL |
| CASE MATERIAL | METAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 0.875 INCHES NOMINAL |
| CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
| FEATURES PROVIDED | TRIP INDICATOR |
| FREQUENCY IN HERTZ | 60.0 SINGLE LOCATION |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 15.0 AMPERES DC SINGLE LOCATION |
| PART NAME ASSIGNED BY CONTROLLING AGENCY | MAGNETIC CIRCUIT BREAKER, 15 AMP, 1 POLE |
| POLE QUANTITY | 1 |
| PROPRIETARY CHARACTERISTICS | PACS |
| MOUNTING FACILITY TYPE AND QUANTITY | 2 CLIP |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.605 INCHES NOMINAL |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC SINGLE LOCATION |
| SPECIAL FEATURES | AP CIRCUIT PROTECTORS WILL TRIP OPEN ON OVERLOAD, EVEN WHEN FORCIBLY HELD ON; WILL OPERERATE AT ANY AMBIENT TEMPERATURE BETWEEN -40 AND +100 DEGREES CELCIUS; INSULATION RESISTANCE EXCEEDS 100 MEGOHOMS AT A POTENTIAL OF 100VDC; WITH WITHSTAND 1250 VOLTS RMS, 60 HZ FROM TERMINALS TO CASE AND BETWEEN THE TERMINALS WHEN OPEN; WITHSTAND 100G SHOCK; WILL NOT BE DAMAGED BY A 10 POUND FORCE APPLIED IN ANY DIRECTION |
| RESET METHOD | MANUAL |
| TERMINAL TYPE AND QUANTITY | 2 SCREW |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.070 MINIMUM AT 200 PCT AND 0.700 MINIMUM AT 200 PCT SINGLE LOCATION |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
| TRIP RELEASE METHOD | MAGNETIC SINGLE LOCATION |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 100.0 SINGLE LOCATION |