| ACTUATOR FUNCTION | TRIP-RESET |
| BODY LENGTH | 2.000 INCHES NOMINAL |
| BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
| BODY WIDTH | 1.515 INCHES MAXIMUM |
| BUSHING LENGTH | 0.240 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.530 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.750 INCHES NOMINAL |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 1.660 INCHES NOMINAL |
| FREQUENCY IN HERTZ | 50.0 OR 60.0 ALL LOCATIONS |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | MOISTURE RESISTANT AND SALT SPRAY PROOF |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| MATERIAL | MICA CASE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 30.0 AMPERES DC ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 3000.0 DC ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE(S) |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.075 INCHES MAXIMUM |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 125.0 DC ALL LOCATIONS |
| POLE QUANTITY | 2 |
| RESET METHOD | MANUAL |
| TERMINAL TYPE AND QUANTITY | 4 QUICK DISCONNECT, MALE |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 1.800 MINIMUM AT 125 PCT AND 100.000 MAXIMUM AT 125 PCT AND 0.006 MINIMUM AT 1000 PCT AND 0.280 MAXIMUM AT 1000 PCT ALL LOCATIONS |
| TRIP RELEASE AMBIENT TEMP RATING | -40.0 CELSIUS MINIMUM AND 85.0 CELSIUS MAXIMUM ALL LOCATIONS |
| TRIP RELEASE DUTY CYCLE | CONTINUOUS ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 135.0 ALL LOCATIONS |
| UNTHREADED MOUNTING HOLE DIAMETER | 0.156 INCHES NOMINAL |