| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT POLE TWO |
| BODY LENGTH | 50.8 MILLIMETERS NOMINAL |
| BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
| BODY WIDTH | 57.5 MILLIMETERS MAXIMUM |
| BUSHING LENGTH | 15.9 MILLIMETERS NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 38.9 MILLIMETERS NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 19.0 MILLIMETERS NOMINAL |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| FREQUENCY IN HERTZ | 50.0 OR 60.0 ALL LOCATIONS |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 15.0 AMPERES AC ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 1 THREADED BUSHING WITH PANEL SEAL |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | 56.7 MILLIMETERS MAXIMUM |
| NOMINAL THREAD SIZE | 0.500 INCHES |
| POLE QUANTITY | 3 |
| RESET METHOD | MANUAL |
| THREAD SERIES DESIGNATOR | UN |
| THREAD QUANTITY PER INCH | 32 |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 10.000 MINIMUM AT 125 PCT AND 120.000 MAXIMUM AT 125 PCT ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |