| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT POLE ONE |
| BODY LENGTH | 1.140 INCHES NOMINAL |
| BODY WIDTH | 0.570 INCHES NOMINAL |
| BODY STYLE | SINGLE POLE TYPE |
| BUSHING LENGTH | 0.400 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 0.780 INCHES NOMINAL |
| CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
| FREQUENCY IN HERTZ | 60.0 SINGLE LOCATION |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF AND FUNGUS RESISTANT |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 PUSH BUTTON |
| MATERIAL | PLASTIC CASE |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 2000.0 AC AND 2000.0 DC SINGLE LOCATION |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 5.0 AMPERES AC AND 5.0 AMPERES DC SINGLE LOCATION |
| MOUNTING FACILITY TYPE AND QUANTITY | 1 THREADED BUSHING |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.220 INCHES NOMINAL |
| NOMINAL THREAD SIZE | 0.375 INCHES |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC AND 28.0 DC SINGLE LOCATION |
| POLE QUANTITY | 1 |
| RESET METHOD | MANUAL |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| SPECIAL FEATURES | THIS ITEM HAS A NEW FEATURE: ON/OFF SWITCH BUILDED WITHIN THE CIRCUIT BREAKER // SPECIFICATIONS: A. MAX VOLTAGE RATINGS(250 VAC & 28 VDC) X B. MAX INTERRUPTING CAPACITY(< 2000 AMP) X C. DIELECTRIC STRENGTH(1500 VAC) X D. INSULATION RESISTANCE(100 MEGOHM) X E. LIFE(6000 CYCLES AT RATED CURRENT) X F. CURRENT RATING(5 AMP) X G. TEMPERATURE RANGE(-40 DEGREE .F TO 160 DEGREE F) |
| TERMINAL TYPE AND QUANTITY | 2 SCREW |
| THREAD QUANTITY PER INCH | 27 |
| THREAD SERIES DESIGNATOR | UNS |
| TRIP RELEASE AMBIENT TEMP RATING | 40.0 CELSIUS NOMINAL SINGLE LOCATION |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
| TRIP RELEASE METHOD | THERMAL SINGLE LOCATION |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 10.000 MINIMUM AT 200 PCT AND 40.000 MAXIMUM AT 200 PCT SINGLE LOCATION |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |