| AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| FREQUENCY IN HERTZ | 60.0 OR 400.0 ALL LOCATIONS |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC AND 50.0 DC ALL LOCATIONS |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 12.5 AMPERES AC AND 12.5 AMPERES DC ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 300.0 AC AND 500.0 DC ALL LOCATIONS |
| POLE QUANTITY | 3 |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.055 MINIMUM AT 200 PCT AND 0.950 MAXIMUM AT 200 PCT ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 135.0 ALL LOCATIONS |