5925-01-396-1121 CIRCUIT BREAKER Index 5925-01-396-1123 CIRCUIT BREAKER

National Stock Number:
5925-01-396-1122

Federal Supply Class:
5925

National Item Identification Number:
013961122

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
87055-01416236DLA LAND AND MARITIME DBA ENGINEERING AND TECHNICAL SUPPORT DIV DOCUMENT STANDARDIZATION DIVISION (VENDOR ITEM DRAWINGS)
87057037Z3DLA LAND AND MARITIME DBA ENGINEERING AND TECHNICAL SUPPORT DIV DOCUMENT STANDARDIZATION DIVISION (DRAWINGS)
87057-014037Z3DLA LAND AND MARITIME DBA ENGINEERING AND TECHNICAL SUPPORT DIV DOCUMENT STANDARDIZATION DIVISION (DRAWINGS)
HM1-230-01474193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
AP1-R-87055-01481541SENSATA TECHNOLOGIES MARYLAND, INC


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
AUXILIARY SWITCH FUNCTION AND QUANTITY1 ALARM
BODY LENGTH1.562 INCHES MAXIMUM
BODY STYLESINGLE POLE TYPE
BODY WIDTH0.625 INCHES MAXIMUM
BUSHING LENGTH0.380 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH0.875 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT SINGLE LOCATION
FREQUENCY IN HERTZ400.0 SINGLE LOCATION
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP SINGLE LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS240.0 AC AND 50.0 DC SINGLE LOCATION
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE1.25 AMPERES AC AND 1.25 AMPERES DC SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS300.0 AC AND 500.0 DC SINGLE LOCATION
MOUNTING FACILITY TYPE AND QUANTITY2 THREADED BUSHING WITH PANEL SEAL
MOUNTING SURFACE TO TERMINAL END DISTANCE1.605 INCHES MAXIMUM
NOMINAL THREAD SIZE0.375 INCHES
POLE QUANTITY1
RESET METHODMANUAL
TRIP RELEASE CHARACTERISTICTIME DELAY SINGLE LOCATION
TRIP RELEASE METHODMAGNETIC ALL LOCATIONS
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT0.500 MINIMUM AT 200 PCT AND 20.000 MAXIMUM AT 200 PCT SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT150.0 SINGLE LOCATION
SWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROW
SWITCH CURRENT RATING AND TYPE IN AMPS0.5 AC AND 0.5 DC
SWITCH LOCATION AND POSITION DESIGNATIONINTERNAL AT POLE ONE
SWITCH TERMINAL TYPETAB, SOLDER LUG
SWITCH VOLTAGE RATING AND TYPE IN VOLTS120.0 AC AND 50.0 DC
TERMINAL TYPE AND QUANTITY2 WIRE HOOK
THREAD SERIES DESIGNATORUNEF


Click here to Register for Free 30-day Trial