5925-01-330-5911 CIRCUIT BREAKER Index 5925-01-330-5913 CIRCUIT BREAKER

National Stock Number:
5925-01-330-5912

Federal Supply Class:
5925

National Item Identification Number:
013305912

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
03-20-0225A96169ELECTRIC BOAT CORPORATION
ETN970710S0630086L3HARRIS MARITIME POWER & ENERGY SOLUTIONS, INC.
TRID 0369 SHEET 5-5- ITEM 7703950NAVAL INVENTORY CONTROL POINT MECHANICSBURG
MIL-C-17361/1381349MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M


Techincal Specification:
ACTUATOR FUNCTIONRESET
BODY LENGTH16.500 INCHES NOMINAL
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPE
BODY WIDTH9.625 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH3.000 INCHES NOMINAL
CIRCUIT PROTECTION TYPEUNDERVOLTAGE ALL LOCATIONS
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS500.0 AC ALL LOCATIONS
MANUAL ACTUATOR TYPE AND QUANTITY1 PUSH-PULL
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS75000.0 AC ALL LOCATIONS
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE1600.0 AMPERES AC ALL LOCATIONS
NONDEFINITIVE SPEC/STD DATAAQB TYPE
POLE QUANTITY3
RESET METHODMANUAL
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT20.000 MINIMUM AT 600 PCT AND 32.000 MAXIMUM AT 600 PCT ALL LOCATIONS
TRIP RELEASE CHARACTERISTICINSTANTANEOUS AND TIME DELAY ALL LOCATIONS
TERMINAL TYPE AND QUANTITY6 BUS BAR