| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT POLE TWO |
| ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| BODY LENGTH | 1.562 INCHES MAXIMUM |
| BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
| BODY WIDTH | 1.937 INCHES MAXIMUM |
| BUSHING LENGTH | 0.332 INCHES MINIMUM AND 0.380 INCHES MAXIMUM |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 0.906 INCHES MAXIMUM |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.594 INCHES MINIMUM AND 0.656 INCHES MAXIMUM |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| FRAGILITY FACTOR | MODERATELY RUGGED |
| FREQUENCY IN HERTZ | 400.0 ALL LOCATIONS |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | HERMETICALLY SEALED |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 4.0 AMPERES AC AND 4.0 AMPERES DC ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 300.0 AC AND 500.0 DC ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 1 THREADED BUSHING WITH PANEL SEAL |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.828 INCHES MAXIMUM |
| NOMINAL THREAD SIZE | 0.375 INCHES |
| NONTURN DEVICE DIAMETER | 0.140 INCHES NOMINAL |
| NONTURN DEVICE LENGTH | 0.130 INCHES NOMINAL |
| NONTURN DEVICE RADIUS | 0.625 INCHES NOMINAL |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC AND 50.0 DC ALL LOCATIONS |
| POLE QUANTITY | 3 |
| RESET METHOD | MANUAL |
| SPECIFICATION/STANDARD DATA | 81349-MIL-C-39019/5 GOVERNMENT SPECIFICATION |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| TERMINAL TYPE AND QUANTITY | 6 WIRE HOOK |
| TEST DATA DOCUMENT | 81349-MIL-C-39019 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.). |
| THREAD QUANTITY PER INCH | 32 |
| THREAD SERIES DESIGNATOR | UNEF |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.055 MINIMUM AT 200 PCT AND 0.950 MAXIMUM AT 200 PCT ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 ALL LOCATIONS |