| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT EACH POLE |
| ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM |
| BODY LENGTH | 5.115 INCHES MINIMUM AND 5.135 INCHES MAXIMUM |
| BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
| BODY WIDTH | 4.144 INCHES MAXIMUM |
| BOSS HEIGHT | 0.209 INCHES MINIMUM AND 0.229 INCHES MAXIMUM |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.016 INCHES MINIMUM AND 1.036 INCHES MAXIMUM |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 3.537 INCHES MINIMUM AND 3.557 INCHES MAXIMUM |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.740 INCHES MINIMUM AND 2.760 INCHES MAXIMUM |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.016 INCHES MINIMUM AND 1.036 INCHES MAXIMUM |
| EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, THREE, AND FOUR LINKED |
| FEATURES PROVIDED | HIGH INRUSH PROTECTION |
| FRAGILITY FACTOR | MODERATELY RUGGED |
| FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS PROOF AND HUMIDITY PROOF AND SALT WATER RESISTANT AND SHOCK RESISTANT AND VIBRATION RESISTANT |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
| MANUAL ACTUATOR TYPE AND QUANTITY | 4 TOGGLE |
| MATERIAL | PLASTIC CASE |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 7500.0 AC ALL LOCATIONS |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 55.0 AMPERES AC ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 8 THREADED HOLE(S) |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.599 INCHES MINIMUM AND 2.619 INCHES MAXIMUM |
| NOMINAL THREAD SIZE | 0.138 INCHES |
| POLE QUANTITY | 4 |
| RESET METHOD | MANUAL |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 20.000 MINIMUM AT 200 PCT AND 105.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
| SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE FOUR |
| SWITCH TERMINAL TYPE | TAB, SOLDER LUG |
| TERMINAL TYPE AND QUANTITY | 8 THREADED STUD |
| THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| THREAD QUANTITY PER INCH | 32 |