5925-01-320-6901 CIRCUIT BREAKER Index 5925-01-320-6903 CIRCUIT BREAKER

National Stock Number:
5925-01-320-6902

Federal Supply Class:
5925

National Item Identification Number:
013206902

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
67Z4-13798437ELLIS & WATTS INTERNATIONAL, LLC
AM3-A3-A-60-274193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
UPL-111-1-62-60381541SENSATA TECHNOLOGIES MARYLAND, INC
IELHK111-1-62-60.0-K-01-V82647SENSATA TECHNOLOGIES, INC.


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT EACH POLE
ARC QUENCHING METHODMAGNETIC BLOWOUT
BODY LENGTH2.380 INCHES MINIMUM AND 2.620 INCHES MAXIMUM
BODY STYLEMULTIPOLE-MULTIPLE ACTUATOR TYPE
BODY WIDTH2.130 INCHES MINIMUM AND 2.370 INCHES MAXIMUM
BOSS HEIGHT0.010 INCHES MINIMUM AND 0.250 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.630 INCHES MINIMUM AND 0.870 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.820 INCHES MINIMUM AND 2.060 INCHES MAXIMUM
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH2.130 INCHES MINIMUM AND 2.370 INCHES MAXIMUM
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH0.630 INCHES MINIMUM AND 0.870 INCHES MAXIMUM
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, AND THREE LINKED
FRAGILITY FACTORMODERATELY RUGGED
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDDUSTPROOF AND FUNGUS PROOF
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS200.0 AC ALL LOCATIONS
MANUAL ACTUATOR TYPE AND QUANTITY3 TOGGLE
MATERIALPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE60.0 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY6 THREADED HOLE(S)
MOUNTING SURFACE TO TERMINAL END DISTANCE2.130 INCHES MINIMUM AND 2.370 INCHES MAXIMUM
NOMINAL THREAD SIZE0.138 INCHES
POLE QUANTITY3
RESET METHODMANUAL
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT2.000 MINIMUM AT 200 PCT AND 20.000 MAXIMUM AT 200 PCT ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
TRIP RELEASE METHODMAGNETIC-HYDRAULIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS
SPECIFICATION/STANDARD DATA98437-67Z4-137 MANUFACTURERS SOURCE CONTROL
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY6 THREADED STUD
THREAD QUANTITY PER INCH32
THREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)