5925-01-315-3805 CIRCUIT BREAKER Index 5330-01-315-3807 PACKING,PREFORMED

National Stock Number:
5925-01-315-3806

Federal Supply Class:
5925

National Item Identification Number:
013153806

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
12-771842-2052414EMERSON ELECTRIC CO COMPUTER POWER DIV
12-771842-2060969GENERAL ELECTRIC CO ELECTRICAL DISTRIBUTION AND CONTROL


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS+1200.0 TO 4000.0 AC AND +1200.0 TO 4000.0 DC ALL LOCATIONS
AUXILIARY SWITCH FUNCTION AND QUANTITY4 ALARM
BODY STYLERECTANGULAR DIMENSIONAL ENVELOPE
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
FEATURES PROVIDEDADJUSTABLE TRIP RELEASE
FRAGILITY FACTORMODERATELY RUGGED
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDGENERAL PURPOSE
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS600.0 AC AND 250.0 DC ALL LOCATIONS
OVERALL HEIGHT5.380 INCHES MAXIMUM
OVERALL LENGTH9.120 INCHES NOMINAL
OVERALL WIDTH8.240 INCHES MINIMUM AND 8.250 INCHES MAXIMUM
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
MATERIALPLASTIC CASE
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS22000.0 AC AND 10000.0 DC ALL LOCATIONS
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE400.0 AMPERES AC AND 400.0 AMPERES DC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY4 UNTHREADED HOLE(S)
SPECIAL FEATURES48 VDC SHUNT TRIP WITH WIRE LEADS INSTALLED ON RIGHT SIDE OF CIRCUIT BREAKER; 120 VAC MOTOR OPERATOR MOUNTED ON FRONT OF CIRCUIT BREAKER,5.750 INCH LG,3.230 INCH W,10.120 INCH H
POLE QUANTITY3
RESET METHODMANUAL
TRIP RELEASE AMBIENT TEMP RATING50.0 CELSIUS NOMINAL ALL LOCATIONS
TRIP RELEASE CHARACTERISTICINSTANTANEOUS ALL LOCATIONS
TRIP RELEASE METHODTHERMAL-MAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS
UNTHREADED MOUNTING HOLE DIAMETER0.310 INCHES NOMINAL
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
SWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROW
SWITCH CURRENT RATING AND TYPE IN AMPS6.0 AC AND 0.250 DC
SWITCH LOCATION AND POSITION DESIGNATIONEXTERNAL AT POLE THREE
SWITCH TERMINAL TYPEWIRE LEAD
SWITCH VOLTAGE RATING AND TYPE IN VOLTS240.0 AC AND 250.0 DC
TERMINAL TYPE AND QUANTITY6 COMPRESSION