| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT POLE TWO |
| AUXILIARY SWITCH FUNCTION AND QUANTITY | 2 ALARM |
| BODY LENGTH | 5.984 INCHES MINIMUM AND 6.015 INCHES MAXIMUM |
| BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
| BODY WIDTH | 4.484 INCHES MINIMUM AND 4.516 INCHES MAXIMUM |
| BOSS HEIGHT | 0.203 INCHES MINIMUM AND 0.235 INCHES MAXIMUM |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 5.109 INCHES MINIMUM AND 5.141 INCHES MAXIMUM |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.484 INCHES MINIMUM AND 1.516 INCHES MAXIMUM |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.484 INCHES MINIMUM AND 1.516 INCHES MAXIMUM |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 4.578 INCHES MINIMUM AND 4.610 INCHES MAXIMUM |
| FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS PROOF AND GENERAL PURPOSE |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| MATERIAL | PLASTIC CASE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 15.0 AMPERES AC ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 15000.0 AC ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE(S) |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | 3.984 INCHES MINIMUM AND 4.015 INCHES MAXIMUM |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
| POLE QUANTITY | 3 |
| RESET METHOD | MANUAL |
| SPECIAL FEATURES | INCLUDES 3 TULIP CONNECTORS FOR LINE SIDE AND 3 TULIP CONNECTORS FOR LOAD SIDE |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
| SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL BETWEEN POLE TWO AND THREE |
| SWITCH TERMINAL TYPE | WIRE LEAD |
| TERMINAL TYPE AND QUANTITY | 6 COMPRESSION |
| TRIP RELEASE AMBIENT TEMP RATING | 40.0 CELSIUS NOMINAL ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS |
| TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
| UNTHREADED MOUNTING HOLE DIAMETER | 0.164 INCHES NOMINAL |