| POLE QUANTITY | 2 |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 3.0 AMPERES AC AND |
| 3.0 AMPERES DC ALL LOCATIONS |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| TERMINAL TYPE AND QUANTITY | 4 QUICK DISCONNECT, MALE |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC AND |
| 65.0 DC ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| RESET METHOD | MANUAL |
| BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
| MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE |
| CASE MATERIAL | PLASTIC |
| TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
| FREQUENCY IN HERTZ | 50.0 OR |
| 60.0 ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC AND |
| 1000.0 DC ALL LOCATIONS |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.150 MINIMUM AT 200 PCT AND |
| 1.500 MAXIMUM AT 200 PCT ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| BODY LENGTH | 1.968 INCHES MINIMUM AND |
| 2.032 INCHES MAXIMUM |
| BODY WIDTH | 1.468 INCHES MINIMUM AND |
| 1.532 INCHES MAXIMUM |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.528 INCHES MINIMUM AND |
| 1.592 INCHES MAXIMUM |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.718 INCHES MINIMUM AND |
| 0.782 INCHES MAXIMUM |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 1.628 INCHES MINIMUM AND |
| 1.692 INCHES MAXIMUM |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.718 INCHES MINIMUM AND |
| 0.782 INCHES MAXIMUM |
| BOSS HEIGHT | 0.098 INCHES MINIMUM AND |
| 0.162 INCHES MAXIMUM |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.898 INCHES MINIMUM AND |
| 1.962 INCHES MAXIMUM |
| THREAD SERIES DESIGNATOR | UNC |
| NOMINAL THREAD SIZE | 0.138 INCHES |
| THREAD QUANTITY PER INCH | 32 |
| MANUAL ACTUATOR TYPE AND QUANTITY | 2 TOGGLE |
| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT EACH POLE |
| EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF |
| ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| FRAGILITY FACTOR | MODERATELY RUGGED |