| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT EACH POLE |
| ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM |
| BODY LENGTH | 2.000 INCHES NOMINAL |
| BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
| BODY WIDTH | 3.015 INCHES MAXIMUM |
| BOSS HEIGHT | 0.130 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.530 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.750 INCHES NOMINAL |
| CIRCUIT PROTECTION TYPE | OVERCURRENT FIRST LOCATION |
| CIRCUIT PROTECTION TYPE | OVERCURRENT SECOND LOCATION |
| CIRCUIT PROTECTION TYPE | OVERCURRENT THIRD LOCATION |
| CIRCUIT PROTECTION TYPE | UNDERVOLTAGE FOURTH LOCATION |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.750 INCHES NOMINAL |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 1.660 INCHES NOMINAL |
| EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, THREE, AND FOUR LINKED |
| FRAGILITY FACTOR | MODERATELY RUGGED |
| FREQUENCY IN HERTZ | 400.0 ALL LOCATIONS |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | MOISTURE RESISTANT AND SHOCK RESISTANT AND VIBRATION RESISTANT |
| INTERNAL TRIP RELEASE CONFIGURATION | RELAY TRIP FOURTH LOCATION |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SECOND LOCATION |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP THIRD LOCATION |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP FIRST LOCATION |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | 4 TOGGLE |
| MATERIAL | PLASTIC CASE |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC AND 1000.0 DC FOURTH LOCATION |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC FIRST LOCATION |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 12.5 AMPERES AC FIRST LOCATION |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 12.5 AMPERES AC SECOND LOCATION |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 12.5 AMPERES AC THIRD LOCATION |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 15.0 AMPERES AC AND 15.0 AMPERES DC FOURTH LOCATION |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC THIRD LOCATION |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC SECOND LOCATION |
| MOUNTING FACILITY TYPE AND QUANTITY | 8 THREADED HOLE(S) |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.032 INCHES MAXIMUM |
| NOMINAL THREAD SIZE | 0.138 INCHES |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC AND 65.0 DC FOURTH LOCATION |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC THIRD LOCATION |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC FIRST LOCATION |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC SECOND LOCATION |
| POLE QUANTITY | 4 |
| RESET METHOD | MANUAL |
| SPECIAL HANDLING FEATURE | MAGNETIC |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| SWITCH TERMINAL TYPE | TAB, SOLDER LUG |
| SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 240.0 AC AND 50.0 DC |
| SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
| SWITCH CURRENT RATING AND TYPE IN AMPS | 5.0 AC AND 3.0 DC |
| SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE ONE |
| TERMINAL TYPE AND QUANTITY | 8 THREADED STUD |
| THREAD PITCH DIAMETERS | +0.1177 TO 0.1214 INCHES |
| THREAD QUANTITY PER INCH | 32 |
| THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.150 MINIMUM AT 200 PCT AND 1.900 MAXIMUM AT 200 PCT ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 ALL LOCATIONS |
| UNPACKAGED UNIT WEIGHT | 8.000 OUNCES NOMINAL |