| BODY LENGTH | 2.500 INCHES NOMINAL2.500 INCHES NOMINAL |
| BODY STYLE | SINGLE POLE TYPESINGLE POLE TYPE |
| BODY WIDTH | 0.750 INCHES NOMINAL0.750 INCHES NOMINAL |
| BOSS HEIGHT | 0.140 INCHES NOMINAL0.140 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.938 INCHES NOMINAL1.938 INCHES NOMINAL |
| CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.062 INCHES NOMINAL2.062 INCHES NOMINAL |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 65.0 DC SINGLE LOCATION |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 DC SINGLE LOCATION |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 20.0 AMPERES DC SINGLE LOCATION |
| MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE(S)4 THREADED HOLE(S) |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.841 INCHES NOMINAL1.841 INCHES NOMINAL |
| NOMINAL THREAD SIZE | 0.138 INCHES |
| POLE QUANTITY | 11 |
| RESET METHOD | MANUAL |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
| TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC SINGLE LOCATION |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 1.400 MINIMUM AT 150 PCT AND 25.000 MAXIMUM AT 150 PCT SINGLE LOCATION |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |
| ULTIMATE TRIP TIME PER POLE IN SECONDS | 2.000 MINIMUM AND 80.000 MAXIMUM SINGLE LOCATION |
| THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |