5310-01-251-3453 WASHER,FLAT Index 5925-01-251-3455 CIRCUIT BREAKER

National Stock Number:
5925-01-251-3454

Federal Supply Class:
5925

National Item Identification Number:
012513454

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
522672-180020NAVAL AIR WARFARE CENTER AIRCRAFT DIVISION CODE 4.8.8.0.0.B BLDG 148-2
JJ3B40030086L3HARRIS MARITIME POWER & ENERGY SOLUTIONS, INC.
JJ63B40030086L3HARRIS MARITIME POWER & ENERGY SOLUTIONS, INC.
JXD63B40030086L3HARRIS MARITIME POWER & ENERGY SOLUTIONS, INC.
JXD63B40066842SIEMENS ENERGY AND AUTOMATION INC ITE CIRCUIT PROTECTION DIV
JJ63B40066842SIEMENS ENERGY AND AUTOMATION INC ITE CIRCUIT PROTECTION DIV


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE TWO
ARC QUENCHING METHODAIRAIR
BODY HEIGHT4.000 INCHES NOMINAL4.000 INCHES NOMINAL
BODY LENGTH11.000 INCHES NOMINAL11.000 INCHES NOMINAL
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPEMULTIPOLE-SINGLE ACTUATOR TYPE
BODY WIDTH7.484 INCHES NOMINAL7.484 INCHES NOMINAL
BOSS HEIGHT0.313 INCHES NOMINAL0.313 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH9.750 INCHES NOMINAL9.750 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH2.500 INCHES NOMINAL2.500 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH9.750 INCHES NOMINAL9.750 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH2.500 INCHES NOMINAL2.500 INCHES NOMINAL
FRAGILITY FACTORMODERATELY RUGGEDMODERATELY RUGGED
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND VIBRATION RESISTANT AND SHOCK RESISTANT
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS600.0 AC ALL LOCATIONS
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
MATERIALPLASTIC CASE
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS25000.0 AC ALL LOCATIONS
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE400.0 AMPERES AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY4 UNTHREADED HOLE(S)4 UNTHREADED HOLE(S)
POLE QUANTITY33
RESET METHODMANUAL
SPECIAL FEATURESCIRCUIT BREAKER MUST BE COMPATIBLE WITH PANELBOARD NAEC PART NUMBER 625226-1
SPECIAL HANDLING FEATUREMAGNETICMAGNETIC
TRIP RELEASE CHARACTERISTICINSTANTANEOUS SINGLE LOCATION
TRIP RELEASE METHODMAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 SINGLE LOCATION
UNTHREADED MOUNTING HOLE DIAMETER0.281 INCHES NOMINAL0.281 INCHES NOMINAL
STORAGE TYPEGENERAL PURPOSE WAREHOUSEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY6 COMPRESSION