012488394

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
D6760-1-2582647SENSATA TECHNOLOGIES, INC.


Techincal Specification:
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH1.812 INCHES NOMINAL
ACTUATOR FUNCTIONTRIP-RESET
BODY HEIGHT2.125 INCHES MAXIMUM
BODY LENGTH2.250 INCHES MAXIMUM
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPE
BODY WIDTH2.203 INCHES MAXIMUM
BUSHING LENGTH0.250 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH1.188 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
FREQUENCY IN HERTZ400.0 ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 PUSH-PULL
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE25.0 AMPERES AC ALL LOCATIONS
POLE QUANTITY3
PROPRIETARY CHARACTERISTICSPACS
MOUNTING FACILITY TYPE AND QUANTITY4 THREADED HOLE
NOMINAL THREAD SIZE0.138 INCHES
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS125.0 AC ALL LOCATIONS
RESET METHODMANUAL
TERMINAL TYPE AND QUANTITY6 TAB W/SCREW
THREAD QUANTITY PER INCH32
THREAD SERIES DESIGNATORUNC
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT10.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 70.000 MAXIMUM AT 200 PCT ALL LOCATIONS AND 2.000 MINIMUM AT 400 PCT ALL LOCATIONS AND 9.000 MAXIMUM AT 400 PCT ALL LOCATIONS AND 0.350 MINIMUM AT 1000 PCT ALL LOCATIONS AND 1.400 MAXIMUM AT 1000 PCT ALL LOCATIONS
TRIP RELEASE AMBIENT TEMP RATING25.0 DEG CELSIUS NOMINAL ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
TRIP RELEASE METHODMAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT138.0 ALL LOCATIONS
ULTIMATE TRIP TIME PER POLE IN SECONDS3600.000 MAXIMUM ALL LOCATIONS