5925-01-247-5945 CIRCUIT BREAKER Index 5925-01-247-5947 CIRCUIT BREAKER

National Stock Number:
5925-01-247-5946

Federal Supply Class:
5925

National Item Identification Number:
012475946

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
NFJ434125LL21810CHALLENGER ELECTRICAL EQUIPMENT CORP


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
ARC QUENCHING METHODAIR
BODY HEIGHT3.750 INCHES NOMINAL
BODY LENGTH9.562 INCHES NOMINAL
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPE
BODY WIDTH4.125 INCHES NOMINAL
BOSS HEIGHT0.375 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH1.375 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH6.749 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
CUBIC MEASURE148.887 CUBIC INCHES
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH6.749 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH0.687 INCHES NOMINAL
FRAGILITY FACTORMODERATELY RUGGED
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS480.0 AC AND 250.0 DC ALL LOCATIONS
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
MATERIALPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE125.0 AMPERES AC AND 125.0 AMPERES DC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS25000.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY4 THREADED HOLE(S)
NOMINAL THREAD SIZE0.190 INCHES
POLE QUANTITY3
RESET METHODMANUAL
TRIP RELEASE CHARACTERISTICINSTANTANEOUS ALL LOCATIONS
TRIP RELEASE METHODMAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY6 SCREW
THREAD SERIES DESIGNATORUNF
THREAD QUANTITY PER INCH32