| ARC QUENCHING METHOD | AIR |
| BODY STYLE | RECTANGULAR DIMENSIONAL ENVELOPE |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| FRAGILITY FACTOR | MODERATELY RUGGED |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| OVERALL HEIGHT | 24.000 INCHES NOMINAL |
| OVERALL LENGTH | 29.125 INCHES NOMINAL |
| OVERALL WIDTH | 25.250 INCHES NOMINAL |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 2600.0 AMPERES DC ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 75000.0 DC ALL LOCATIONS |
| POLE QUANTITY | 2 |
| RESET METHOD | MANUAL |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| TRIP RELEASE AMBIENT TEMP RATING | 40.0 CELSIUS NOMINAL ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS |
| TRIP RELEASE METHOD | THERMAL ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 ALL LOCATIONS |