| POLE QUANTITY | 3 |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 25.0 AMPERES AC FIRST LOCATION |
| 25.0 AMPERES AC SECOND LOCATION |
| 5.0 AMPERES AC THIRD LOCATION |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| TERMINAL TYPE AND QUANTITY | 6 SCREW |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY FIRST LOCATION |
| TIME DELAY SECOND LOCATION |
| INSTANTANEOUS THIRD LOCATION |
| RESET METHOD | MANUAL |
| BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
| MOUNTING FACILITY TYPE AND QUANTITY | 6 THREADED HOLE |
| CASE MATERIAL | PLASTIC |
| TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
| FREQUENCY IN HERTZ | 50.0 OR |
| 60.0 ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC ALL LOCATIONS |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP FIRST LOCATION |
| SERIES TRIP SECOND LOCATION |
| RELAY TRIP THIRD LOCATION |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 2.200 MINIMUM AT 200 PCT AND |
| 20.000 MAXIMUM AT 200 PCT FIRST LOCATION |
| 2.200 MINIMUM AT 200 PCT AND |
| 20.000 MAXIMUM AT 200 PCT SECOND LOCATION |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| BUSHING LENGTH | 0.130 INCHES NOMINAL |
| BODY LENGTH | 2.000 INCHES NOMINAL |
| BODY WIDTH | 2.250 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.531 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.750 INCHES NOMINAL |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 1.656 INCHES NOMINAL |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.750 INCHES NOMINAL |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.898 INCHES NOMINAL |
| THREAD SERIES DESIGNATOR | UNC |
| NOMINAL THREAD SIZE | 0.138 INCHES |
| THREAD QUANTITY PER INCH | 32 |
| MANUAL ACTUATOR TYPE AND QUANTITY | 3 TOGGLE |
| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT EACH POLE |
| EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
| FEATURES PROVIDED | HIGH INRUSH PROTECTION |
| ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| SPECIAL HANDLING FEATURE | MAGNETIC |
| FRAGILITY FACTOR | MODERATELY RUGGED |
| SPECIAL FEATURES | RELAY COIL HAS A SPECIAL ELECTRICAL SHORT FOR MECHANICAL TRIP |