| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT POLE TWO |
| ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS | +1500.0 TO 3000.0 AC ALL LOCATIONS |
| BODY STYLE | RECTANGULAR DIMENSIONAL ENVELOPERECTANGULAR DIMENSIONAL ENVELOPE |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| CRITICALITY CODE JUSTIFICATION | FEAT |
| FEATURES PROVIDED | ADJUSTABLE TRIP RELEASEADJUSTABLE TRIP RELEASE |
| FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| OVERALL HEIGHT | 6.812 INCHES NOMINAL6.812 INCHES NOMINAL |
| OVERALL LENGTH | 12.000 INCHES NOMINAL12.000 INCHES NOMINAL |
| OVERALL WIDTH | 9.000 INCHES NOMINAL9.000 INCHES NOMINAL |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 175.0 AMPERES AC ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 5 UNTHREADED HOLE(S)5 UNTHREADED HOLE(S) |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 500.0 AC ALL LOCATIONS |
| POLE QUANTITY | 33 |
| SPECIAL FEATURES | CAN ONLY BE SAFELY USED WITH NEW TYPE FUSE |
| UNTHREADED MOUNTING HOLE DIAMETER | 0.203 INCHES NOMINAL0.203 INCHES NOMINAL |
| TERMINAL TYPE AND QUANTITY | 6 COMPRESSION |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 270.000 NOMINAL AT 200 PCT ALL LOCATIONS |
| TRIP RELEASE AMBIENT TEMP RATING | 50.0 CELSIUS NOMINAL ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND TIME DELAY ALL LOCATIONS |
| TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |