| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT EACH POLE |
| BODY HEIGHT | 3.359 INCHES NOMINAL |
| BODY LENGTH | 5.125 INCHES NOMINAL |
| BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
| BODY WIDTH | 3.078 INCHES NOMINAL |
| BOSS HEIGHT | 0.219 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 3.547 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.026 INCHES NOMINAL |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.026 INCHES NOMINAL |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.750 INCHES NOMINAL |
| EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
| FRAGILITY FACTOR | MODERATELY RUGGED |
| FREQUENCY IN HERTZ | 50.0 OR 60.0 ALL LOCATIONS |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND MOISTURE RESISTANT |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | 3 TOGGLE |
| MATERIAL | PLASTIC CASE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 35.0 AMPERES AC SECOND LOCATION |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 35.0 AMPERES AC THIRD LOCATION |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 6 THREADED HOLE(S) |
| NOMINAL THREAD SIZE | 0.138 INCHES |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC SECOND LOCATION |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC THIRD LOCATION |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 90.0 AC FIRST LOCATION |
| POLE QUANTITY | 3 |
| RESET METHOD | MANUAL |
| SPECIAL FEATURES | POLE ONE IS A SERIES TRIP COIL AT 35 AMPS AC |
| SPECIAL HANDLING FEATURE | MAGNETIC |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| TERMINAL TYPE AND QUANTITY | 9 THREADED STUD |
| THREAD QUANTITY PER INCH | 32 |
| THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 2.000 MINIMUM AT 200 PCT AND 10.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
| UNPACKAGED UNIT WEIGHT | 2.000 POUNDS NOMINAL |