| TRIP RELEASE CHARACTERISTIC | TIME DELAY SECOND LOCATION |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY THIRD LOCATIONTIME DELAY SECOND LOCATION |
| TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
| UNPACKAGED UNIT WEIGHT | 9.000 OUNCES NOMINAL |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| TERMINAL TYPE AND QUANTITY | 7 THREADED STUD |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 1.648 INCHES MINIMUM AND 1.675 INCHES MAXIMUM |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.745 INCHES MINIMUM AND 0.755 INCHES MAXIMUM |
| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT EACH POLE |
| ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| AUXILIARY TRIP COIL VOLTAGE TYPE AND RATING IN VOLTS | 120.0 DC NOMINAL FIRST LOCATION |
| BODY LENGTH | 1.985 INCHES MINIMUM AND 2.015 INCHES MAXIMUM |
| BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
| BODY WIDTH | 2.265 INCHES MAXIMUM |
| BOSS HEIGHT | 0.115 INCHES MINIMUM AND 0.145 INCHES MAXIMUM |
| CASE MATERIAL | PLASTIC |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.648 INCHES MINIMUM AND 1.675 INCHES MAXIMUM |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.735 INCHES MINIMUM AND 0.765 INCHES MAXIMUM |
| CIRCUIT PROTECTION TYPE | OVERCURRENT SECOND LOCATION |
| CIRCUIT PROTECTION TYPE | OVERCURRENT THIRD LOCATIONOVERCURRENT SECOND LOCATION |
| CIRCUIT PROTECTION TYPE | UNDERVOLTAGE FIRST LOCATION |
| EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
| FRAGILITY FACTOR | MODERATELY RUGGED |
| FREQUENCY IN HERTZ | 50.0 OR 60.0 SECOND LOCATION50.0 OR 60.0 THIRD LOCATION |
| FREQUENCY IN HERTZ | 50.0 OR 60.0 THIRD LOCATION |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | SHOCK RESISTANT AND VIBRATION RESISTANT AND SALT SPRAY PROOF AND MOISTURE RESISTANT |
| NOMINAL THREAD SIZE | 0.138 INCHES |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 120.0 DC FIRST LOCATION |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC THIRD LOCATION250.0 AC SECOND LOCATION |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC SECOND LOCATION |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SECOND LOCATION |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP THIRD LOCATIONSERIES TRIP SECOND LOCATION |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP W/REMOTE TRIP FEATURE FIRST LOCATION |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | 3 TOGGLE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 30.0 AMPERES DC FIRST LOCATION |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 30.0 AMPERES AC SECOND LOCATION |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 30.0 AMPERES AC THIRD LOCATION30.0 AMPERES AC SECOND LOCATION |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 3500.0 AC THIRD LOCATION |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 3500.0 AC SECOND LOCATION |
| MOUNTING FACILITY TYPE AND QUANTITY | 8 THREADED HOLE |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.032 INCHES MAXIMUM |
| RESET METHOD | MANUAL |
| POLE QUANTITY | 3 |
| SPECIAL FEATURES | POLE 1 MUST TURN ON WHEN 120 VDC IS APPLIED |
| THREAD QUANTITY PER INCH | 32 |
| THREAD SERIES DESIGNATOR | UNC |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 2.000 MINIMUM AT 200 PCT AND 20.000 MAXIMUM AT 200 PCT SECOND LOCATION |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 2.000 MINIMUM AT 200 PCT AND 20.000 MAXIMUM AT 200 PCT THIRD LOCATION |
| TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS FIRST LOCATION |
| TRIP RELEASE DUTY CYCLE | CONTINUOUS FIRST LOCATION |