| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| FEATURES PROVIDED | ADJUSTABLE TRIP RELEASE |
| FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 500.0 AC ALL LOCATIONS |
| OVERALL HEIGHT | 15.000 INCHES NOMINAL |
| OVERALL LENGTH | 25.937 INCHES NOMINAL |
| OVERALL WIDTH | 21.500 INCHES NOMINAL |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 400.0 AMPERES AC ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 34000.0 AC ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 8 UNTHREADED HOLE |
| POLE QUANTITY | 3 |
| RESET METHOD | MANUAL |
| TRIP RELEASE AMBIENT TEMP RATING | 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS |
| TRIP RELEASE METHOD | THERMAL ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 ALL LOCATIONS |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT POLE ONE |
| ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS | +640.0 TO 960.0 AC ALL LOCATIONS |
| ARC QUENCHING METHOD | AIR |
| BODY STYLE | RECTANGULAR DIMENSIONAL ENVELOPE |
| CASE MATERIAL | PLASTIC |