5925-01-180-0079 CIRCUIT BREAKER Index 5925-01-180-0081 CIRCUIT BREAKER

National Stock Number:
5925-01-180-0080

Federal Supply Class:
5925

National Item Identification Number:
011800080

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
985611-00216224TITAN CORP THE
985611-00263702L-3 SERVICES, INC. DBA COMMAND & CONTROL SYSTEMS SOFTWARE & EXPEDITIONARY OPERATION
APG-6668-1REC3-8420-281541SENSATA TECHNOLOGIES MARYLAND, INC


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE TWO AND AT POLE THREE
AUXILIARY SWITCH FUNCTION AND QUANTITY1 ALARM
BODY LENGTH2.000 INCHES NOMINAL
BODY STYLEMULTIPOLE-MULTIPLE ACTUATOR TYPE
BODY WIDTH3.015 INCHES MAXIMUM
BUSHING LENGTH0.130 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.530 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.750 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH0.750 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH1.660 INCHES NOMINAL
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTTWO AND THREE LINKED
FREQUENCY IN HERTZ50.0 OR 60.0 SECOND LOCATION
FREQUENCY IN HERTZ50.0 OR 60.0 THIRD LOCATION
FREQUENCY IN HERTZ50.0 OR 60.0 FIRST LOCATION
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP FIRST LOCATION
INTERNAL TRIP RELEASE CONFIGURATIONRELAY TRIP FOURTH LOCATION
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP SECOND LOCATION
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP THIRD LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY2 TOGGLE
MATERIALPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE5.0 AMPERES AC FIRST LOCATION
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE5.0 AMPERES AC SECOND LOCATION
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE5.0 AMPERES AC THIRD LOCATION
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE30.0 AMPERES DC FOURTH LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 AC FIRST LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 AC SECOND LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 AC THIRD LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS2000.0 DC FOURTH LOCATION
MOUNTING FACILITY TYPE AND QUANTITY8 THREADED HOLE(S)
MOUNTING SURFACE TO TERMINAL END DISTANCE2.032 INCHES MAXIMUM
NOMINAL THREAD SIZE0.138 INCHES
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS65.0 DC FOURTH LOCATION
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS250.0 AC FIRST LOCATION
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS250.0 AC SECOND LOCATION
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS250.0 AC THIRD LOCATION
POLE QUANTITY4
RESET METHODMANUAL
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
SWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROW
SWITCH CURRENT RATING AND TYPE IN AMPS10.0 AC AND 3.0 DC
SWITCH LOCATION AND POSITION DESIGNATIONINTERNAL AT POLE ONE
SWITCH TERMINAL TYPETAB, SOLDER LUG
SWITCH VOLTAGE RATING AND TYPE IN VOLTS250.0 AC AND 50.0 DC
TERMINAL TYPE AND QUANTITY10 TAB W/SCREW
THREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
THREAD QUANTITY PER INCH32
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT0.130 MINIMUM AT 200 PCT AND 1.300 MAXIMUM AT 200 PCT FIRST LOCATION
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT0.130 MINIMUM AT 200 PCT AND 1.300 MAXIMUM AT 200 PCT SECOND LOCATION
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT0.130 MINIMUM AT 200 PCT AND 1.300 MAXIMUM AT 200 PCT THIRD LOCATION
TRIP RELEASE CHARACTERISTICINSTANTANEOUS FOURTH LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY SECOND LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY THIRD LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY FIRST LOCATION
TRIP RELEASE METHODMAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 FIRST LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 SECOND LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 THIRD LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT150.0 FOURTH LOCATION


Click here to Register for Free 30-day Trial