| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT EACH POLE |
| ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| BODY LENGTH | 2.480 INCHES MINIMUM AND 2.500 INCHES MAXIMUM |
| BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
| BODY WIDTH | 1.500 INCHES MAXIMUM |
| BOSS HEIGHT | 0.150 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.940 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.750 INCHES NOMINAL |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.750 INCHES NOMINAL |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.050 INCHES MINIMUM AND 2.070 INCHES MAXIMUM |
| EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
| FEATURES PROVIDED | SLIDING BAR INTERLOCK |
| FRAGILITY FACTOR | MODERATELY RUGGED |
| FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | HERMETICALLY SEALED AND SHOCK RESISTANT AND VIBRATION RESISTANT |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | 2 TOGGLE |
| MATERIAL | PLASTIC CASE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 15.0 AMPERES AC FIRST LOCATION |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 7.5 AMPERES AC SECOND LOCATION |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 2000.0 AC AND 1000.0 AC ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE(S) |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.475 INCHES NOMINAL |
| NOMINAL THREAD SIZE | 0.138 INCHES |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 120.0 AC AND 250.0 AC ALL LOCATIONS |
| POLE QUANTITY | 2 |
| RESET METHOD | MANUAL |
| SPECIAL HANDLING FEATURE | MAGNETIC |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| TERMINAL TYPE AND QUANTITY | 4 THREADED STUD |
| THREAD PITCH DIAMETERS | +0.1177 TO 0.1214 INCHES |
| THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 10.000 MINIMUM AT 200 PCT AND 60.000 MAXIMUM AT 200 PCT AND 1.900 MINIMUM AT 400 PCT AND 8.000 MAXIMUM AT 400 PCT AND 0.600 MINIMUM AT 600 PCT AND 2.500 MAXIMUM AT 600 PCT ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 115.0 ALL LOCATIONS |
| ULTIMATE TRIP TIME PER POLE IN SECONDS | 80.000 MINIMUM AND 650.000 MAXIMUM ALL LOCATIONS |
| UNPACKAGED UNIT WEIGHT | 7.400 OUNCES NOMINAL |