| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | BETWEEN POLE ONE AND TWO |
| BODY HEIGHT | 1.555 INCHES MAXIMUM |
| BODY LENGTH | 2.000 INCHES NOMINAL |
| BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
| BODY WIDTH | 1.540 INCHES NOMINAL |
| BOSS HEIGHT | 0.125 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.625 INCHES NOMINAL |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| FREQUENCY IN HERTZ | 50.0 OR 60.0 FIRST LOCATION |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT |
| INTERNAL TRIP RELEASE CONFIGURATION | RELAY TRIP SECOND LOCATION |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP FIRST LOCATION |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| MATERIAL | PLASTIC CASE |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC AND 1000.0 DC ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 2 CLIP |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 120.0 AC FIRST LOCATION |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 24.0 DC SECOND LOCATION |
| POLE QUANTITY | 2 |
| RESET METHOD | MANUAL |
| TERMINAL TYPE AND QUANTITY | 6 QUICK DISCONNECT, MALE |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.500 MINIMUM AT 200 PCT AND 9.000 MAXIMUM AT 200 PCT FIRST LOCATION |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.050 MAXIMUM AT 200 PCT AND 0.025 MAXIMUM AT 300 PCT SECOND LOCATION |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |