5925-01-111-4507 CIRCUIT BREAKER Index 5925-01-111-4509 CIRCUIT BREAKER

National Stock Number:
5925-01-111-4508

Federal Supply Class:
5925

National Item Identification Number:
011114508

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
203-14-6267-181541SENSATA TECHNOLOGIES MARYLAND, INC


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONBETWEEN POLE ONE AND TWO
BODY HEIGHT1.555 INCHES MAXIMUM
BODY LENGTH2.000 INCHES NOMINAL
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPE
BODY WIDTH1.540 INCHES NOMINAL
BOSS HEIGHT0.125 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.625 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
FREQUENCY IN HERTZ50.0 OR 60.0 FIRST LOCATION
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT
INTERNAL TRIP RELEASE CONFIGURATIONRELAY TRIP SECOND LOCATION
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP FIRST LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
MATERIALPLASTIC CASE
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 AC AND 1000.0 DC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY2 CLIP
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS120.0 AC FIRST LOCATION
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS24.0 DC SECOND LOCATION
POLE QUANTITY2
RESET METHODMANUAL
TERMINAL TYPE AND QUANTITY6 QUICK DISCONNECT, MALE
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT0.500 MINIMUM AT 200 PCT AND 9.000 MAXIMUM AT 200 PCT FIRST LOCATION
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT0.050 MAXIMUM AT 200 PCT AND 0.025 MAXIMUM AT 300 PCT SECOND LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
TRIP RELEASE METHODMAGNETIC-HYDRAULIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS