5925-01-107-8785 CIRCUIT BREAKER Index 5925-01-107-8789 CIRCUIT BREAKER

National Stock Number:
5925-01-107-8786

Federal Supply Class:
5925

National Item Identification Number:
011078786

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
0134191FP59IKON SYSTEMS INC
Q11530086L3HARRIS MARITIME POWER & ENERGY SOLUTIONS, INC.
Q11560555SIEMENS-ALLIS INC
Q11584588FRANKLIN ELECTRIC CO INC


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
BODY HEIGHT2.375 INCHES NOMINAL
BODY LENGTH3.125 INCHES NOMINAL
BODY STYLESINGLE POLE TYPE
BODY WIDTH1.000 INCHES NOMINAL
BOSS HEIGHT0.187 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT SINGLE LOCATION
FREQUENCY IN HERTZ60.0 SINGLE LOCATION
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS240.0 AC SINGLE LOCATION
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
MATERIALPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE15.0 AMPERES AC SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS10000.0 AC SINGLE LOCATION
MOUNTING FACILITY TYPE AND QUANTITY2 SLOT
MOUNTING SLOT WIDTH0.094 INCHES NOMINAL
POLE QUANTITY1
RESET METHODMANUAL
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT120.000 MAXIMUM AT 200 PCT SINGLE LOCATION
TRIP RELEASE AMBIENT TEMP RATING40.0 CELSIUS NOMINAL SINGLE LOCATION
TRIP RELEASE CHARACTERISTICINSTANTANEOUS AND TIME DELAY SINGLE LOCATION
TRIP RELEASE METHODTHERMAL-MAGNETIC SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT135.0 SINGLE LOCATION
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY1 CLIP AND 1 SCREW BASE