5935-01-107-6620 SOCKET,PLUG-IN ELECTRONIC COMPON Index 5925-01-107-6622 CIRCUIT BREAKER

National Stock Number:
5925-01-107-6621

Federal Supply Class:
5925

National Item Identification Number:
011076621

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
78200225-00133322GETRONICS GOVERNMENT SOLUTIONS LLC
78201094-00433322GETRONICS GOVERNMENT SOLUTIONS LLC
JA2-Y4-274193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
JA2-Z244-174193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
UPGH41-4253-181541SENSATA TECHNOLOGIES MARYLAND, INC


Techincal Specification:
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT2.000 MINIMUM AT 200 PCT AND 20.000 MAXIMUM AT 200 PCT ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
TRIP RELEASE METHODMAGNETIC-HYDRAULIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS
UNPACKAGED UNIT WEIGHT6.000 OUNCES NOMINAL
SPECIAL HANDLING FEATUREMAGNETIC
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY4 SCREW
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH1.510 INCHES MINIMUM AND 1.675 INCHES MAXIMUM
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH0.735 INCHES MINIMUM AND 0.765 INCHES MAXIMUM
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT EACH POLE
BODY LENGTH1.985 INCHES MINIMUM AND 2.015 INCHES MAXIMUM
BODY STYLEMULTIPOLE-MULTIPLE ACTUATOR TYPE
BODY WIDTH1.515 INCHES MAXIMUM
BOSS HEIGHT0.115 INCHES MINIMUM AND 0.145 INCHES MAXIMUM
CASE MATERIALPLASTIC
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.515 INCHES MINIMUM AND 1.545 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.735 INCHES MINIMUM AND 0.765 INCHES MAXIMUM
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE AND TWO LINKED
FRAGILITY FACTORMODERATELY RUGGED
FREQUENCY IN HERTZ50.0 OR 60.0 SECOND LOCATION
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDCORROSION RESISTANT AND MOISTURE RESISTANT AND SHOCKPROOF AND VIBRATIONPROOF
NOMINAL THREAD SIZE0.138 INCHES
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS250.0 AC SECOND LOCATION
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS6.5 DC FIRST LOCATION
INTERNAL TRIP RELEASE CONFIGURATIONRELAY TRIP FIRST LOCATION
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP SECOND LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY2 TOGGLE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE3.0 AMPERES AC SECOND LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY4 THREADED HOLE
MOUNTING SURFACE TO TERMINAL END DISTANCE2.032 INCHES MAXIMUM
RESET METHODMANUAL
POLE QUANTITY2
SPECIAL FEATURESPOLE ONE IS A SWITCH ONLY
THREAD QUANTITY PER INCH32
THREAD SERIES DESIGNATORUNC


Click here to Register for Free 30-day Trial