5935-01-102-1508 SOCKET,PLUG-IN ELECTRONIC COMPON Index 5935-01-102-1510 CONNECTOR,PLUG,ELECTRICAL

National Stock Number:
5925-01-102-1509

Federal Supply Class:
5925

National Item Identification Number:
011021509

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
5050513-157958SIGNALS WARFARE PROJECT MANAGER
7822070-00798747OGDEN AIR LOGISTICS CENTER
KD1-21W134EATON CORP AEROSPACE COMMERCIAL CONTROLS DIV
KD1-274193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV


Techincal Specification:
ACTUATOR FUNCTIONRESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
BODY LENGTH2.150 INCHES NOMINAL
BODY STYLESINGLE POLE TYPE
CIRCUIT PROTECTION TYPEOVERCURRENT SINGLE LOCATION
FREQUENCY IN HERTZ50.0 OR 60.0 SINGLE LOCATION
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDGENERAL PURPOSE
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP SINGLE LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 PUSH BUTTON
OVERALL DIAMETER0.750 INCHES NOMINAL
MATERIALPLASTIC CASE
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 AC AND 1000.0 DC SINGLE LOCATION
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE500.0 MILLIAMPERES AC AND 500.0 MILLIAMPERES DC SINGLE LOCATION
MOUNTING FACILITY TYPE AND QUANTITY1 CLIP
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS240.0 AC AND 32.0 DC SINGLE LOCATION
POLE QUANTITY1
RESET METHODMANUAL
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY2 QUICK DISCONNECT, MALE
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT3.500 MINIMUM AT 200 PCT AND 9.500 MAXIMUM AT 200 PCT SINGLE LOCATION
TRIP RELEASE AMBIENT TEMP RATING25.0 CELSIUS NOMINAL SINGLE LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY SINGLE LOCATION
TRIP RELEASE METHODTHERMAL SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT135.0 SINGLE LOCATION