5925-01-097-1743 CIRCUIT BREAKER Index 5925-01-097-1746 CIRCUIT BREAKER

National Stock Number:
5925-01-097-1744

Federal Supply Class:
5925

National Item Identification Number:
010971744

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
CD3-A8-DU-72-120/240-10074193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
SM-A-776904-6211447L3 TECHNOLOGIES, INC.
SM-A-776904-6249671LOCKHEED MARTIN CORP LOCKHEED MARTIN INFORMATION SYSTEMS AUTOMATED SPARES
SM-A-776904-6280063US ARMY COMMUNICATIONS & ELECTRONICS MATERIEL READINESS COMMAND LOGISTICS ENGINEERING DIR


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT EACH POLE
ARC QUENCHING METHODMAGNETIC BLOWOUT
BODY HEIGHT3.485 INCHES NOMINAL
BODY LENGTH4.750 INCHES NOMINAL
BODY STYLEMULTIPOLE-MULTIPLE ACTUATOR TYPE
BODY WIDTH3.108 INCHES MAXIMUM
BOSS HEIGHT0.219 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH1.026 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH3.547 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH2.750 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH1.539 INCHES NOMINAL
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, AND THREE LINKED
FEATURES PROVIDEDHIGH INRUSH PROTECTION
FRAGILITY FACTORMODERATELY RUGGED
FREQUENCY IN HERTZ66.0 ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDVIBRATION RESISTANT AND SHOCK RESISTANT
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS240.0 AC ALL LOCATIONS
MANUAL ACTUATOR TYPE AND QUANTITY3 TOGGLE
MATERIALPLASTIC CASE
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 AC ALL LOCATIONS
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE72.0 AMPERES AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY6 THREADED HOLE(S) AND 6 UNTHREADED HOLE(S)
NOMINAL THREAD SIZE0.138 INCHES
POLE QUANTITY3
RESET METHODMANUAL
SPECIAL HANDLING FEATUREMAGNETIC
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
TRIP RELEASE METHODMAGNETIC ALL LOCATIONS
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT10.500 MINIMUM AT 200 PCT AND 60.000 MAXIMUM AT 200 PCT ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS
UNPACKAGED UNIT WEIGHT2.000 POUNDS NOMINAL
UNTHREADED MOUNTING HOLE DIAMETER0.151 INCHES MINIMUM AND 0.161 INCHES MAXIMUM
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY6 THREADED STUD
THREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
THREAD QUANTITY PER INCH32