5910-01-096-5888 CAPACITOR,FIXED,METALLIZED,PAPER Index 5925-01-096-5892 CIRCUIT BREAKER

National Stock Number:
5925-01-096-5890

Federal Supply Class:
5925

National Item Identification Number:
010965890

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
69732700-0627963GENERAL DYNAMICS INFORMATION SYSTEMS INC. DBA GENERAL DYNAMICS ADVANCED INFORMATION SYSTEMS
69732700-063CYA2GENERAL DYNAMICS MISSION SYSTEMS, INC.
AP-112-4047-0681541SENSATA TECHNOLOGIES MARYLAND, INC


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE TWO
ARC QUENCHING METHODMAGNETIC BLOWOUT
BODY LENGTH1.500 INCHES MAXIMUM
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPE
BODY WIDTH1.875 INCHES MAXIMUM
BUSHING LENGTH0.250 INCHES MINIMUM AND 0.312 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH0.844 INCHES MINIMUM AND 0.906 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.594 INCHES MINIMUM AND 0.656 INCHES MAXIMUM
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
FRAGILITY FACTORMODERATELY RUGGED
FREQUENCY IN HERTZ430.0 ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDHERMETICALLY SEALED AND MOISTURE RESISTANT AND FUNGUS RESISTANT
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 AC ALL LOCATIONS
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE15.0 AMPERES AC THIRD LOCATION
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE25.0 AMPERES AC FIRST LOCATION
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE25.0 AMPERES AC SECOND LOCATION
MOUNTING FACILITY TYPE AND QUANTITY1 THREADED BUSHING WITH PANEL SEAL
MOUNTING SURFACE TO TERMINAL END DISTANCE1.780 INCHES MAXIMUM
NOMINAL THREAD SIZE0.375 INCHES
NONTURN DEVICE RADIUS0.610 INCHES MINIMUM AND 0.640 INCHES MAXIMUM
NONTURN DEVICE DIAMETER0.235 INCHES MINIMUM AND 0.265 INCHES MAXIMUM
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS120.0 AC ALL LOCATIONS
POLE QUANTITY3
RESET METHODMANUAL
SPECIAL HANDLING FEATUREMAGNETIC
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY6 WIRE HOOK
THREAD QUANTITY PER INCH32
THREAD SERIES DESIGNATORUNEF
THREAD PITCH DIAMETERS+0.3503 TO 0.3537 INCHES
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT0.200 MINIMUM AT 200 PCT AND 6.000 MAXIMUM AT 200 PCT ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
TRIP RELEASE METHODMAGNETIC-HYDRAULIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS
UNPACKAGED UNIT WEIGHT11.100 OUNCES NOMINAL