5925-01-096-4663 CIRCUIT BREAKER Index 5925-01-096-4665 CIRCUIT BREAKER

National Stock Number:
5925-01-096-4664

Federal Supply Class:
5925

National Item Identification Number:
010964664

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
W-C-375/1881348FEDERAL SPECIFICATIONS PROMULGATED BY GENERAL SERVICES ADMINISTRATION WASHINGTON DC
WC375/18-00181348FEDERAL SPECIFICATIONS PROMULGATED BY GENERAL SERVICES ADMINISTRATION WASHINGTON DC


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE TWO
BODY HEIGHT3.365 INCHES MINIMUM AND 3.385 INCHES MAXIMUM
BODY LENGTH5.990 INCHES MINIMUM AND 6.010 INCHES MAXIMUM
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPE
BODY WIDTH4.115 INCHES MINIMUM AND 4.135 INCHES MAXIMUM
BOSS HEIGHT0.115 INCHES MINIMUM AND 0.135 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH5.366 INCHES MINIMUM AND 5.386 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH1.365 INCHES MINIMUM AND 1.385 INCHES MAXIMUM
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH1.365 INCHES MINIMUM AND 1.385 INCHES MAXIMUM
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH4.490 INCHES MINIMUM AND 4.510 INCHES MAXIMUM
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
MATERIALPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE10.0 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS14000.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY4 UNTHREADED HOLE(S)
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS480.0 AC ALL LOCATIONS
POLE QUANTITY3
RESET METHODMANUAL
SPECIFICATION/STANDARD DATA81348-W-C-375/18 GOVERNMENT SPECIFICATION
UNTHREADED MOUNTING HOLE DIAMETER0.188 INCHES NOMINAL
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY6 COMPRESSION
TEST DATA DOCUMENT81348-W-C-375 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.).
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT120.000 MAXIMUM AT 200 PCT ALL LOCATIONS
TRIP RELEASE AMBIENT TEMP RATING40.0 CELSIUS NOMINAL ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
TRIP RELEASE METHODTHERMAL-MAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS