5310-01-095-5732 WASHER,SPRING TENSION Index 5330-01-095-5734 SEAL,PLAIN ENCASED

National Stock Number:
5925-01-095-5733

Federal Supply Class:
5925

National Item Identification Number:
010955733

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
TED13403560969GENERAL ELECTRIC CO ELECTRICAL DISTRIBUTION AND CONTROL
TED134C503560969GENERAL ELECTRIC CO ELECTRICAL DISTRIBUTION AND CONTROL


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE TWO
BODY STYLERECTANGULAR DIMENSIONAL ENVELOPE
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
OVERALL HEIGHT3.812 INCHES NOMINAL
OVERALL LENGTH6.312 INCHES NOMINAL
OVERALL WIDTH4.125 INCHES NOMINAL
MATERIALPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE35.0 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS14000.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY4 UNTHREADED HOLE(S)
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS600.0 AC ALL LOCATIONS
POLE QUANTITY3
RESET METHODMANUAL
UNTHREADED MOUNTING HOLE DIAMETER0.250 INCHES NOMINAL
TERMINAL TYPE AND QUANTITY6 COMPRESSION
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT8.000 MINIMUM AT 300 PCT AND 40.000 MAXIMUM AT 300 PCT ALL LOCATIONS
TRIP RELEASE AMBIENT TEMP RATING50.0 CELSIUS NOMINAL ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
TRIP RELEASE METHODTHERMAL-MAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT138.0 ALL LOCATIONS