| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT POLE TWO |
| ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| BODY LENGTH | 1.985 INCHES MINIMUM AND 2.015 INCHES MAXIMUM |
| BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
| BODY WIDTH | 2.265 INCHES MAXIMUM |
| BUSHING LENGTH | 0.480 INCHES MINIMUM AND 0.510 INCHES MAXIMUM |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.515 INCHES MINIMUM AND 1.545 INCHES MAXIMUM |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.735 INCHES MINIMUM AND 0.765 INCHES MAXIMUM |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| FRAGILITY FACTOR | MODERATELY RUGGED |
| FREQUENCY IN HERTZ | 50.0 OR 60.0 ALL LOCATIONS |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | MOISTURE RESISTANT AND SALT SPRAY PROOF AND SHOCK RESISTANT AND VIBRATION RESISTANT |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| MATERIAL | PLASTIC CASE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 20.0 AMPERES AC ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 1 THREADED BUSHING WITH PANEL SEAL |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.232 INCHES MAXIMUM |
| NOMINAL THREAD SIZE | 0.500 INCHES |
| NONTURN DEVICE DIAMETER | 0.151 INCHES MINIMUM AND 0.161 INCHES MAXIMUM |
| NONTURN DEVICE LENGTH | 0.115 INCHES MINIMUM AND 0.145 INCHES MAXIMUM |
| NONTURN DEVICE RADIUS | 0.641 INCHES MINIMUM AND 0.671 INCHES MAXIMUM |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 277.0 AC ALL LOCATIONS |
| POLE QUANTITY | 3 |
| RESET METHOD | MANUAL |
| SPECIAL HANDLING FEATURE | MAGNETIC |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| TERMINAL TYPE AND QUANTITY | 6 QUICK DISCONNECT, MALE |
| THREAD SERIES DESIGNATOR | UN |
| THREAD QUANTITY PER INCH | 32 |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 10.000 MINIMUM AT 200 PCT AND 70.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
| UNPACKAGED UNIT WEIGHT | 9.000 OUNCES NOMINAL |