CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
458D509G14/369D074G0389946EATON CORPORATION
ETN2743-1130086L3HARRIS MARITIME POWER & ENERGY SOLUTIONS, INC.
ETN2753-1130086L3HARRIS MARITIME POWER & ENERGY SOLUTIONS, INC.


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE TWO
ARC QUENCHING METHODAIR
AUXILIARY SWITCH FUNCTION AND QUANTITY1 ALARM
BODY LENGTH10.000 INCHES NOMINAL
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPE
BODY WIDTH4.125 INCHES NOMINAL
BOSS HEIGHT0.812 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH5.562 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH2.750 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH2.750 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH2.625 INCHES NOMINAL
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, AND THREE LINKED
FRAGILITY FACTORMODERATELY DELICATE
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDDUSTPROOF
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
MATERIALPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE75.0 AMPERES AC AND 75.0 AMPERES DC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS15000.0 AC AND 15000.0 DC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY4 UNTHREADED HOLE(S)
MOUNTING SURFACE TO TERMINAL END DISTANCE6.250 INCHES NOMINAL
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS500.0 AC AND 250.0 DC ALL LOCATIONS
POLE QUANTITY3
RESET METHODMANUAL
SWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROW
SWITCH CURRENT RATING AND TYPE IN AMPS15.0 AC AND 0.5 DC
SWITCH LOCATION AND POSITION DESIGNATIONINTERNAL AT POLE ONE
SWITCH TERMINAL TYPECOMPRESSION
SWITCH VOLTAGE RATING AND TYPE IN VOLTS460.0 AC AND 250.0 DC
TERMINAL TYPE AND QUANTITY6 COMPRESSION
TRIP RELEASE AMBIENT TEMP RATING50.0 CELSIUS NOMINAL ALL LOCATIONS
TRIP RELEASE CHARACTERISTICINSTANTANEOUS ALL LOCATIONS
TRIP RELEASE METHODTHERMAL-MAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT150.0 ALL LOCATIONS
UNPACKAGED UNIT WEIGHT5.500 POUNDS NOMINAL
UNTHREADED MOUNTING HOLE DIAMETER0.281 INCHES NOMINAL