| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE |
| MANUAL ACTUATOR TYPE AND QUANTITY | 2 TOGGLE |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.750 INCHES NOMINAL |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| RESET METHOD | MANUAL |
| BOSS HEIGHT | 0.130 INCHES NOMINAL |
| FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
| EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
| BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.750 INCHES NOMINAL |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC ALL LOCATIONS |
| TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
| THREAD QUANTITY PER INCH | 32 |
| CASE MATERIAL | PLASTIC |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.560 INCHES NOMINAL |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 2.0 AMPERES AC ALL LOCATIONS |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| BODY WIDTH | 1.500 INCHES NOMINAL |
| NOMINAL THREAD SIZE | 0.138 INCHES |
| ACTUATOR FUNCTION | TRIP-RESET |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 1.660 INCHES NOMINAL |
| BODY LENGTH | 2.000 INCHES NOMINAL |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 2.000 MINIMUM AT 200 PCT AND 20.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| THREAD SERIES DESIGNATOR | UNC |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.880 INCHES NOMINAL |
| UNPACKAGED UNIT WEIGHT | 4.250 OUNCES NOMINAL |
| POLE QUANTITY | 2 |
| ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| TERMINAL TYPE AND QUANTITY | 4 QUICK DISCONNECT, MALE |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC ALL LOCATIONS |
| ACTUATOR POSITION DESIGNATION | AT EACH POLE |