5925-01-045-5144 CIRCUIT BREAKER Index 5925-01-045-5146 CIRCUIT BREAKER

National Stock Number:
5925-01-045-5145

Federal Supply Class:
5925

National Item Identification Number:
010455145

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
AM1-B2-A-15-274193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESETTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONEAT POLE ONE
ARC QUENCHING METHODAIRAIR
AUXILIARY SWITCH FUNCTION AND QUANTITY1 ALARM1 ALARM
BODY LENGTH2.490 INCHES MINIMUM AND 2.490 INCHES MINIMUM AND 2.510 INCHES MAXIMUM2.510 INCHES MAXIMUM
BODY STYLESINGLE POLE TYPESINGLE POLE TYPE
BODY WIDTH0.740 INCHES MINIMUM AND 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM0.760 INCHES MAXIMUM
BOSS HEIGHT0.130 INCHES MINIMUM AND 0.130 INCHES MINIMUM AND 0.150 INCHES MAXIMUM0.150 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.928 INCHES MINIMUM AND 1.928 INCHES MINIMUM AND 1.948 INCHES MAXIMUM1.948 INCHES MAXIMUM
CIRCUIT PROTECTION TYPEOVERCURRENT SINGLE LOCATIONOVERCURRENT SINGLE LOCATION
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH2.052 INCHES MINIMUM AND 2.052 INCHES MINIMUM AND 2.072 INCHES MAXIMUM2.072 INCHES MAXIMUM
FRAGILITY FACTORMODERATELY RUGGEDMODERATELY RUGGED
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDDUSTPROOFDUSTPROOF
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP SINGLE LOCATIONSERIES TRIP SINGLE LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREETRIP FREE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS65.0 DC SINGLE LOCATION65.0 DC SINGLE LOCATION
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE1 TOGGLE
MATERIALPLASTIC CASEPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE15.0 AMPERES DC SINGLE LOCATION15.0 AMPERES DC SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 DC SINGLE LOCATION1000.0 DC SINGLE LOCATION
MOUNTING FACILITY TYPE AND QUANTITY2 THREADED HOLE(S)2 THREADED HOLE(S)
MOUNTING SURFACE TO TERMINAL END DISTANCE2.611 INCHES NOMINAL2.611 INCHES NOMINAL
NOMINAL THREAD SIZE0.138 INCHES0.138 INCHES
POLE QUANTITY11
RESET METHODMANUALMANUAL
SPECIAL HANDLING FEATUREMAGNETICMAGNETIC
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT0.600 MINIMUM AT 200 PCT AND 0.600 MINIMUM AT 200 PCT AND 7.000 MAXIMUM AT 200 PCT SINGLE LOCATION7.000 MAXIMUM AT 200 PCT SINGLE LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY SINGLE LOCATIONTIME DELAY SINGLE LOCATION
TRIP RELEASE METHODMAGNETIC-HYDRAULIC SINGLE LOCATIONMAGNETIC-HYDRAULIC SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT135.0 SINGLE LOCATION135.0 SINGLE LOCATION
STORAGE TYPEGENERAL PURPOSE WAREHOUSEGENERAL PURPOSE WAREHOUSE
SWITCH LOCATION AND POSITION DESIGNATIONINTERNAL AT POLE ONEINTERNAL AT POLE ONE
SWITCH TERMINAL TYPETAB, SOLDER LUGTAB, SOLDER LUG
SWITCH VOLTAGE RATING AND TYPE IN VOLTS250.0 AC250.0 AC
SWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROWSINGLE POLE, DOUBLE THROW
SWITCH CURRENT RATING AND TYPE IN AMPS10.0 AC10.0 AC
TERMINAL TYPE AND QUANTITY2 THREADED STUD2 THREADED STUD
THREAD QUANTITY PER INCH3232
THREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)UNIFIED NATIONAL COARSE (UNC)


Click here to Register for Free 30-day Trial