| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT POLE TWO |
| ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS | +600.0 TO 700.0 DC ALL LOCATIONS |
| AUXILIARY SWITCH FUNCTION AND QUANTITY | 2 ALARM |
| BODY LENGTH | 6.500 INCHES NOMINAL |
| BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
| BODY WIDTH | 4.125 INCHES NOMINAL |
| BOSS HEIGHT | 0.187 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.375 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 5.562 INCHES NOMINAL |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| CRITICALITY CODE JUSTIFICATION | FEAT |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.625 INCHES NOMINAL |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 2.750 INCHES NOMINAL |
| FEATURES PROVIDED | INTERCHANGEABLE TRIP RELEASE |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND MOISTURE RESISTANT |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 DC ALL LOCATIONS |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| MATERIAL | PLASTIC CASE |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 DC ALL LOCATIONS |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 5.0 AMPERES AC AND 5.0 AMPERES DC ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE(S) |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | 3.875 INCHES NOMINAL |
| POLE QUANTITY | 3 |
| PRECIOUS MATERIAL AND LOCATION | CONTACTS SILVER |
| PRECIOUS MATERIAL | SILVER |
| RESET METHOD | MANUAL |
| SPECIAL FEATURES | ITEM MUST COMPLY WITH REQUIREMENTS OF DESC PRODUCTION STANDARD NO. L02317; @FOR NAVY NUCLEAR PROPULSION PLANT PRODUCTS ONLY |
| TRIP RELEASE AMBIENT TEMP RATING | 50.0 CELSIUS NOMINAL ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS |
| TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 ALL LOCATIONS |
| UNTHREADED MOUNTING HOLE DIAMETER | 0.281 INCHES NOMINAL |
| SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
| SWITCH TERMINAL TYPE | WIRE LEAD |
| TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |