| ACTUATOR FUNCTION | TRIP-RESETTRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT POLE ONEAT POLE ONE |
| ARC QUENCHING METHOD | MAGNETIC BLOWOUTMAGNETIC BLOWOUT |
| AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM1 ALARM |
| BODY LENGTH | 1.985 INCHES MINIMUM AND 1.985 INCHES MINIMUM AND 2.015 INCHES MAXIMUM2.015 INCHES MAXIMUM |
| BODY STYLE | SINGLE POLE TYPESINGLE POLE TYPE |
| BODY WIDTH | 0.740 INCHES MINIMUM AND 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM0.760 INCHES MAXIMUM |
| BOSS HEIGHT | 0.120 INCHES MINIMUM AND 0.120 INCHES MINIMUM AND 0.140 INCHES MAXIMUM0.140 INCHES MAXIMUM |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.550 INCHES MINIMUM AND 1.550 INCHES MINIMUM AND 1.570 INCHES MAXIMUM1.570 INCHES MAXIMUM |
| CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATIONOVERCURRENT SINGLE LOCATION |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 1.650 INCHES MINIMUM AND 1.650 INCHES MINIMUM AND 1.670 INCHES MAXIMUM1.670 INCHES MAXIMUM |
| FRAGILITY FACTOR | MODERATELY RUGGEDMODERATELY RUGGED |
| FREQUENCY IN HERTZ | 50.0 OR 50.0 OR 60.0 SINGLE LOCATION60.0 SINGLE LOCATION |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | MOISTURE RESISTANTMOISTURE RESISTANT |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATIONSERIES TRIP SINGLE LOCATION |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREETRIP FREE |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC SINGLE LOCATION250.0 AC SINGLE LOCATION |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE1 TOGGLE |
| MATERIAL | PLASTIC CASEPLASTIC CASE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 30.0 AMPERES DC SINGLE LOCATION30.0 AMPERES DC SINGLE LOCATION |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC SINGLE LOCATION1000.0 AC SINGLE LOCATION |
| MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE(S)2 THREADED HOLE(S) |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.870 INCHES MINIMUM AND 1.870 INCHES MINIMUM AND 1.890 INCHES MAXIMUM1.890 INCHES MAXIMUM |
| NOMINAL THREAD SIZE | 0.138 INCHES0.138 INCHES |
| POLE QUANTITY | 11 |
| PRECIOUS MATERIAL AND LOCATION | CONTACT SURFACES SILVERCONTACT SURFACES SILVER |
| PRECIOUS MATERIAL | SILVERSILVER |
| RESET METHOD | MANUALMANUAL |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 2.200 MINIMUM AT 200 PCT AND 2.200 MINIMUM AT 200 PCT AND 20.000 MAXIMUM AT 200 PCT SINGLE LOCATION20.000 MAXIMUM AT 200 PCT SINGLE LOCATION |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATIONTIME DELAY SINGLE LOCATION |
| TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC SINGLE LOCATIONMAGNETIC-HYDRAULIC SINGLE LOCATION |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION125.0 SINGLE LOCATION |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSEGENERAL PURPOSE WAREHOUSE |
| SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE ONEINTERNAL AT POLE ONE |
| SWITCH TERMINAL TYPE | QUICK DISCONNECT, MALEQUICK DISCONNECT, MALE |
| SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 250.0 AC AND 250.0 AC AND 24.0 DC24.0 DC |
| SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROWSINGLE POLE, DOUBLE THROW |
| SWITCH CURRENT RATING AND TYPE IN AMPS | 1.5 AC AND 1.5 AC AND 0.05 DC0.05 DC |
| TERMINAL TYPE AND QUANTITY | 3 QUICK DISCONNECT, MALE3 QUICK DISCONNECT, MALE |
| THREAD QUANTITY PER INCH | 3232 |
| THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC)UNIFIED NATIONAL COARSE (UNC) |