| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 150.0 AMPERES AC ALL LOCATIONS |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| TERMINAL TYPE AND QUANTITY | 4 SCREW BASE |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC AND |
| 250.0 DC ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND |
| TIME DELAY ALL LOCATIONS |
| RESET METHOD | MANUAL |
| BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
| MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
| CASE MATERIAL | PLASTIC |
| TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
| FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 25000.0 AC AND |
| 10000.0 DC ALL LOCATIONS |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 100.000 MINIMUM AT 200 PCT AND |
| 300.000 MAXIMUM AT 200 PCT AND |
| 50.000 MINIMUM AT 250 PCT AND |
| 140.000 MAXIMUM AT 250 PCT AND |
| 30.000 MINIMUM AT 300 PCT AND |
| 80.000 MAXIMUM AT 300 PCT ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| UNTHREADED MOUNTING HOLE DIAMETER | 0.190 INCHES NOMINAL |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| ACTUATOR FUNCTION | TRIP W/SEPARATE RESET |