5925-01-029-3309 CIRCUIT BREAKER Index 5925-01-029-3312 CIRCUIT BREAKER

National Stock Number:
5925-01-029-3311

Federal Supply Class:
5925

National Item Identification Number:
010293311

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
3179574-001853711NAVAL SEA SYSTEMS COMMAND
3179574-1810001NAVAIR AND NAVSEA MANAGED ORIGINAL DESIGN ACTIVITY DWG NOT MATERIAL/PARTS SUPPLIER
3179574-1836090LOCKHEED MARTIN LIBRASCOPE CORP


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESETTRIP-RESET
ACTUATOR POSITION DESIGNATIONBETWEEN POLE ONE AND TWOBETWEEN POLE ONE AND TWO
ARC QUENCHING METHODMAGNETIC BLOWOUTMAGNETIC BLOWOUT
AUXILIARY SWITCH FUNCTION AND QUANTITY1 ALARM1 ALARM
BODY LENGTH1.562 INCHES MAXIMUM1.562 INCHES MAXIMUM
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPEMULTIPOLE-SINGLE ACTUATOR TYPE
BODY WIDTH1.937 INCHES MAXIMUM1.937 INCHES MAXIMUM
BUSHING LENGTH0.280 INCHES MINIMUM AND 0.280 INCHES MINIMUM AND 0.380 INCHES MAXIMUM0.380 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.687 INCHES NOMINAL0.687 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH0.906 INCHES MAXIMUM0.906 INCHES MAXIMUM
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONSOVERCURRENT ALL LOCATIONS
FRAGILITY FACTORMODERATELY RUGGEDMODERATELY RUGGED
FREQUENCY IN HERTZ400.0 ALL LOCATIONS400.0 ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND FUNGUS RESISTANT AND VIBRATION RESISTANT AND VIBRATION RESISTANT AND MOISTURE RESISTANT AND MOISTURE RESISTANT AND SHOCK RESISTANT AND SHOCK RESISTANT AND SALT SPRAY PROOFSALT SPRAY PROOF
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONSSERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREETRIP FREE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS240.0 AC ALL LOCATIONS240.0 AC ALL LOCATIONS
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE1 TOGGLE
MATERIALPLASTIC CASEPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE1.0 AMPERES AC ALL LOCATIONS1.0 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS300.0 AC ALL LOCATIONS300.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY1 THREADED BUSHING WITH PANEL SEAL1 THREADED BUSHING WITH PANEL SEAL
MOUNTING SURFACE TO TERMINAL END DISTANCE1.828 INCHES MAXIMUM1.828 INCHES MAXIMUM
NOMINAL THREAD SIZE0.375 INCHES0.375 INCHES
NONTURN DEVICE DIAMETER0.180 INCHES MINIMUM AND 0.180 INCHES MINIMUM AND 0.300 INCHES MAXIMUM0.300 INCHES MAXIMUM
NONTURN DEVICE RADIUS0.625 INCHES NOMINAL0.625 INCHES NOMINAL
POLE QUANTITY22
RESET METHODMANUALMANUAL
SPECIAL HANDLING FEATUREMAGNETICMAGNETIC
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT0.200 MINIMUM AT 200 PCT AND 0.200 MINIMUM AT 200 PCT AND 6.000 MAXIMUM AT 200 PCT ALL LOCATIONS6.000 MAXIMUM AT 200 PCT ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONSTIME DELAY ALL LOCATIONS
TRIP RELEASE METHODMAGNETIC ALL LOCATIONSMAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT138.0 ALL LOCATIONS138.0 ALL LOCATIONS
STORAGE TYPEGENERAL PURPOSE WAREHOUSEGENERAL PURPOSE WAREHOUSE
SWITCH LOCATION AND POSITION DESIGNATIONINTERNAL AT POLE TWOINTERNAL AT POLE TWO
SWITCH TERMINAL TYPEPINPIN
SWITCH VOLTAGE RATING AND TYPE IN VOLTS120.0 AC AND 120.0 AC AND 50.0 DC50.0 DC
SWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROWSINGLE POLE, DOUBLE THROW
SWITCH CURRENT RATING AND TYPE IN AMPS0.5 AC AND 0.5 AC AND 0.5 DC0.5 DC
TERMINAL TYPE AND QUANTITY4 WIRE HOOK4 WIRE HOOK
TEST DATA DOCUMENT10001-3179574 DRAWING (THIS IS THE BASIC GOVERNING DRAWING, SUCH AS A CONTRACTOR DRAWING, ORIGINAL EQUIPMENT MANUFACTURER DRAWING, ETC.; EXCLUDES ANY SPECIFICATION, STANDARD OR OTHER DOCUMENT THAT MAY BE REFERENCED IN A BASIC GOVERNING DRAWING)10001-3179574 DRAWING (THIS IS THE BASIC GOVERNING DRAWING, SUCH AS A CONTRACTOR DRAWING, ORIGINAL EQUIPMENT MANUFACTURER DRAWING, ETC.; EXCLUDES ANY SPECIFICATION, STANDARD OR OTHER DOCUMENT THAT MAY BE REFERENCED IN A BASIC GOVERNING DRAWING)
THREAD QUANTITY PER INCH3232
THREAD SERIES DESIGNATORUNEFUNEF