| ACTUATOR FUNCTION | TRIP-RESETTRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT POLE ONEAT POLE ONE |
| BODY HEIGHT | 2.312 INCHES NOMINAL2.312 INCHES NOMINAL |
| BODY LENGTH | 3.000 INCHES NOMINAL3.000 INCHES NOMINAL |
| BODY STYLE | SINGLE POLE TYPESINGLE POLE TYPE |
| BODY WIDTH | 0.734 INCHES NOMINAL0.734 INCHES NOMINAL |
| BOSS HEIGHT | 0.156 INCHES NOMINAL0.156 INCHES NOMINAL |
| CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATIONOVERCURRENT SINGLE LOCATION |
| FREQUENCY IN HERTZ | 60.0 SINGLE LOCATION60.0 SINGLE LOCATION |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATIONSERIES TRIP SINGLE LOCATION |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREETRIP FREE |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC SINGLE LOCATION240.0 AC SINGLE LOCATION |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE1 TOGGLE |
| MATERIAL | PLASTIC CASEPLASTIC CASE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 20.0 AMPERES AC SINGLE LOCATION20.0 AMPERES AC SINGLE LOCATION |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC SINGLE LOCATION10000.0 AC SINGLE LOCATION |
| MOUNTING FACILITY TYPE AND QUANTITY | 1 TERMINAL1 TERMINAL |
| POLE QUANTITY | 11 |
| RESET METHOD | MANUALMANUAL |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 120.000 MAXIMUM AT 200 PCT SINGLE LOCATION120.000 MAXIMUM AT 200 PCT SINGLE LOCATION |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATIONTIME DELAY SINGLE LOCATION |
| TRIP RELEASE METHOD | MAGNETIC SINGLE LOCATIONMAGNETIC SINGLE LOCATION |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION125.0 SINGLE LOCATION |
| TERMINAL TYPE AND QUANTITY | 1 CLIP AND 1 CLIP AND 1 SCREW1 SCREW |