| ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM |
| BODY STYLE | RECTANGULAR DIMENSIONAL ENVELOPE |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| FRAGILITY FACTOR | MODERATELY RUGGED |
| FREQUENCY IN HERTZ | 400.0 ALL LOCATIONS |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | CORROSION RESISTANT AND HUMIDITY RESISTANT AND MOISTURE RESISTANT AND FUNGUS RESISTANT |
| INTERNAL TRIP RELEASE CONFIGURATION | RELAY TRIP ALL LOCATIONS |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| OVERALL HEIGHT | 3.920 INCHES MAXIMUM |
| OVERALL LENGTH | 6.120 INCHES MAXIMUM |
| OVERALL WIDTH | 4.950 INCHES MAXIMUM |
| MATERIAL | PLASTIC CASE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 275.0 AMPERES AC AND 275.0 AMPERES DC ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE(S) |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 200.0 AC AND 28.0 DC ALL LOCATIONS |
| POLE QUANTITY | 3 |
| RESET METHOD | MANUAL |
| UNTHREADED MOUNTING HOLE DIAMETER | 0.214 INCHES MINIMUM AND 0.228 INCHES MAXIMUM |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
| SWITCH CURRENT RATING AND TYPE IN AMPS | 7.5 AC |
| SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE THREE |
| TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |
| TRIP RELEASE AMBIENT TEMP RATING | 40.0 CELSIUS NOMINAL ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS |
| TRIP RELEASE METHOD | THERMAL ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
| UNPACKAGED UNIT WEIGHT | 4.500 POUNDS NOMINAL |