5950-00-981-9004 CHOKE Index 6625-00-981-9008 MULTIMETER

National Stock Number:
5925-00-981-9006

Federal Supply Class:
5925

National Item Identification Number:
009819006

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
224204510001NAVAIR AND NAVSEA MANAGED ORIGINAL DESIGN ACTIVITY DWG NOT MATERIAL/PARTS SUPPLIER


Techincal Specification:
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT145.0 ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
BUSHING LENGTH0.500 INCHES NOMINAL
BODY LENGTH2.000 INCHES MAXIMUM
BODY WIDTH0.850 INCHES MAXIMUM
MOUNTING SURFACE TO TERMINAL END DISTANCE2.765 INCHES MAXIMUM
THREAD SERIES DESIGNATORUNS
NOMINAL THREAD SIZE0.469 INCHES
THREAD QUANTITY PER INCH32
MANUAL ACTUATOR TYPE AND QUANTITY1 PUSH-PULL
ACTUATOR FUNCTIONTRIP-RESET
POLE QUANTITY3
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE1.0 AMPERES AC AND
1.0 AMPERES DC ALL LOCATIONS
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
TERMINAL TYPE AND QUANTITY6 TAB W/SCREW
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS120.0 AC AND
28.0 DC ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
RESET METHODMANUAL
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPE
MOUNTING FACILITY TYPE AND QUANTITY1 THREADED BUSHING
TRIP RELEASE METHODTHERMAL ALL LOCATIONS
FREQUENCY IN HERTZ400.0 ALL LOCATIONS
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
TRIP RELEASE AMBIENT TEMP RATING25.0 DEG CELSIUS NOMINAL ALL LOCATIONS
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT2.000 MINIMUM AT 200 PCT AND
20.000 MAXIMUM AT 200 PCT ALL LOCATIONS
ACTUATOR POSITION DESIGNATIONAT EACH POLE
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDDUSTPROOF AND
WATERTIGHT
THE MANUFACTURERS DATA
MANUFACTURERS CODE10001
DESIGN CONTROL REFERENCE2242045


Click here to Register for Free 30-day Trial