| POLE QUANTITY | 3 |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 30.0 AMPERES AC ALL LOCATIONS |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND |
| TIME DELAY ALL LOCATIONS |
| RESET METHOD | MANUAL |
| MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
| TRIP RELEASE METHOD | THERMAL ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 7500.0 AC ALL LOCATIONS |
| TRIP RELEASE DUTY CYCLE | CONTINUOUS ALL LOCATIONS |
| TRIP RELEASE AMBIENT TEMP RATING | 25.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 30.000 MINIMUM AT 150 PCT AND |
| 240.000 MAXIMUM AT 150 PCT AND |
| 3.000 MINIMUM AT 500 PCT AND |
| 5.000 MAXIMUM AT 500 PCT ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 115.0 ALL LOCATIONS |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| OVERALL LENGTH | 13.093 INCHES NOMINAL |
| OVERALL HEIGHT | 9.625 INCHES NOMINAL |
| OVERALL WIDTH | 4.687 INCHES NOMINAL |
| NOMINAL THREAD SIZE | 0.250 INCHES |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| ACTUATOR FUNCTION | TRIP-RESET |
| ARC QUENCHING METHOD | DEION |
| SPECIAL FEATURES | FLUSH MTD ON 11.750 IN. BY 8.000 IN. MTG CENTERS |
| THE MANUFACTURERS DATA | |
| MANUFACTURERS CODE | 30086 |
| DESIGN CONTROL REFERENCE | ET1573E1 |