| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| FEATURES PROVIDED | ADJUSTABLE TRIP RELEASE |
| FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | EXPLOSION PROOF |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 200.0 AMPERES AC AND 200.0 AMPERES DC ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 42000.0 AC AND 42000.0 DC ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 2 UNTHREADED HOLE(S) |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC AND 250.0 DC ALL LOCATIONS |
| POLE QUANTITY | 3 |
| RESET METHOD | MANUAL |
| TERMINAL TYPE AND QUANTITY | 6 SCREW |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 5.000 MINIMUM AT 200 PCT AND 20.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
| UNTHREADED MOUNTING HOLE DIAMETER | 0.562 INCHES NOMINAL |