| ACTUATOR FUNCTION | RESET |
| ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.062 INCHES NOMINAL |
| FREQUENCY IN HERTZ | 60.0 SINGLE LOCATION |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | EXPLOSION PROOF AND FUNGUS RESISTANT AND MOISTURE RESISTANT |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| OVERALL HEIGHT | 2.530 INCHES NOMINAL |
| OVERALL LENGTH | 3.330 INCHES NOMINAL |
| OVERALL WIDTH | 0.760 INCHES NOMINAL |
| MATERIAL | PLASTIC CASE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 7.5 AMPERES AC SINGLE LOCATION |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC SINGLE LOCATION |
| MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE(S) |
| NOMINAL THREAD SIZE | 0.138 INCHES |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC SINGLE LOCATION |
| POLE QUANTITY | 1 |
| RESET METHOD | MANUAL |
| TERMINAL TYPE AND QUANTITY | 2 THREADED STUD |
| THREAD QUANTITY PER INCH | 32 |
| THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.600 MINIMUM AT 150 PCT AND 2.000 MAXIMUM AT 150 PCT AND 0.250 MINIMUM AT 200 PCT AND 0.800 MAXIMUM AT 200 PCT AND 0.090 MINIMUM AT 300 PCT AND 0.190 MAXIMUM AT 300 PCT SINGLE LOCATION |
| TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND TIME DELAY SINGLE LOCATION |
| TRIP RELEASE METHOD | MAGNETIC SINGLE LOCATION |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |