5950-00-906-7810 TRANSFORMER,POWER Index 3040-00-906-7812 SHAFT,SHOULDERED

National Stock Number:
5925-00-906-7811

Federal Supply Class:
5925

National Item Identification Number:
009067811

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
CH22015605EATON CORP OPNS & TECHNICAL CENTER
CH22027192DRS NAVAL POWER SYSTEMS INC
EC2020SFC27192DRS NAVAL POWER SYSTEMS INC
W-C-375/681348FEDERAL SPECIFICATIONS PROMULGATED BY GENERAL SERVICES ADMINISTRATION WASHINGTON DC
WC375/06-00281348FEDERAL SPECIFICATIONS PROMULGATED BY GENERAL SERVICES ADMINISTRATION WASHINGTON DC
W-C-375/681349MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M
WC375/06-00281349MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT EACH POLE
BODY HEIGHT2.466 INCHES MINIMUM AND 2.594 INCHES MAXIMUM
BODY LENGTH2.987 INCHES MINIMUM AND 3.013 INCHES MAXIMUM
BODY STYLEMULTIPOLE-MULTIPLE ACTUATOR TYPE
BODY WIDTH1.464 INCHES MINIMUM AND 1.496 INCHES MAXIMUM
BOSS HEIGHT0.188 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.552 INCHES MINIMUM AND 0.578 INCHES MAXIMUM
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE AND TWO LINKED
FRAGILITY FACTORMODERATELY RUGGED
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDCORROSION RESISTANT
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY2 TOGGLE
MATERIALPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE20.0 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS10000.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY2 TERMINAL
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS240.0 AC ALL LOCATIONS
POLE QUANTITY2
RESET METHODMANUAL
SPECIAL HANDLING FEATUREMAGNETIC
SPECIFICATION/STANDARD DATA81349-W-C-375/6 GOVERNMENT SPECIFICATION
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY4 CLIP
TEST DATA DOCUMENT81348-W-C-375 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.).
TRIP RELEASE AMBIENT TEMP RATING40.0 CELSIUS NOMINAL ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
TRIP RELEASE METHODTHERMAL-MAGNETIC ALL LOCATIONS
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT2.000 MAXIMUM AT 200 PCT ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT135.0 ALL LOCATIONS


Click here to Register for Free 30-day Trial